Assigning the data array
parameters
19
02/02 AWB27-1300-GB
Changing parameters
The set data array parameters can be modified in the
following way:
X
Save the function block under another name.
X
Change the desired parameters in the variables
declaration.
X
Check your changes by checking syntax using (ALT+F10).
The modified function block is available for further use in the
list of application-specific function blocks.
Examples
Two remote partner stations are connected to a central
station via a dial-up modem. The partner stations only
communicate via the central station. The central station
sends 5 bytes to the partner stations (service 12) and
receives 30 bytes from them (service 15). To do this, the
following settings must be made in the variables
declarations of the central and partner stations:
Central station
The function block “TCMT1zU2“ is used for the central
station. The above-mentioned parameters result in a 70 byte
data memory requirement.