01/08 AWB2190-1430GB
Description of parameters
applicable to RA-SP
131
F-22 Mains failure duration (IPS)
With the default settings, each fault triggers a fault message. An
automatic restart is possible after the following fault messages
have occurred:
• Overcurrent (E01 to E04, up to four restart attempts within ten
minutes before a fault message is issued)
• Overvoltage (E07 and E15, up to three restart attempts within
then minutes, then fault signal)
• Undervoltage (E09, up to 16 restart attempts within 10
minutes, then a fault message is issued)
“Diagnostics and troubleshooting”, page 113
With PNU b01, specify the restarting behaviour.
With PNU b02 and b03, specify the behaviour on mains failure
(
a
fig. 125 and fig. 126).
j
Danger!
In the event of a fault, this function causes an automatic
restart of the RA-SP after the set delay when a Start signal
is applied (through AS-Interface
®
) or if an operating
direction is enabled in manual mode (selector switch).
Ensure that an automatic restart does not present a
danger for personnel.
Figure 125: Motor frequency lower than set under PNU b02
U
LN
: Supply voltage
U
2
: Output voltage
n
M
: Motor speed
t
0
: Duration of supply failure
a
Free run stop (coasting)
Figure 126: Duration of power failure longer than set under PNU b02
U
LN
: Supply voltage
U
2
: Output voltage
n
M
: Motor speed
t
0
: Duration of supply failure
a
Free run stop (coasting)
PNU b02
PNU b03
U
LN
U
2
n
M
t
O
a
PNU b02
U
LN
U
2
n
M
t
O
a
Содержание Rapid Link
Страница 10: ...01 08 AWB2190 1430GB 6 ...
Страница 40: ...01 08 AWB2190 1430GB 36 ...
Страница 48: ...01 08 AWB2190 1430GB 44 ...
Страница 70: ...01 08 AWB2190 1430GB 66 ...
Страница 145: ...01 08 AWB2190 1430GB Parameterization with DrivesSoft 141 Figure 134 Example acceleration time ...
Страница 146: ...01 08 AWB2190 1430GB 142 ...
Страница 162: ...01 08 AWB2190 1430GB 158 ...