EMC Suitable Wiring
67
05/01 AWB2700-1384GB
5
Wiring:
Conductors should always be laid on both sides to assure good
attenuation of disturbances in the high frequency range.
The conductors should be laid on one side if only attenuation of the
low frequency range is necessary. One-sided installation is
advantageous if
• a bonding conductor cannot be installed
• Film shieldings are used
Potential Compensation
Potential differences can occur in installation components that are
in separate areas and which
X
are fed by different supplies,
X
are fed by different networks,
X
have double-sided conductor shields which are grounded on
different installation components.
The potential difference between data reference potentials DGND
of all connections (minimal wiring with shielding of two bus
subscribers) must not exceed ± 7 V. If this cannot be guaranteed
then a potential compensation must be created.
In the case of stationary bus operation, the shielded cable should
be insulated and laid on the shielding rail.
Fixing of the cable to the shielding rail should be carried out
using metal cable clips. These clips must cover the rail over a
large surface area. The cable must be routed directly after it
enters the switching cabinet to the shielding rail. Then, it has to
be routed to the connection point - without being laid again!
Содержание DP-16DI-ECO
Страница 12: ...8 05 01 AWB2700 1384GB ...
Страница 16: ...12 05 01 AWB2700 1384GB ...
Страница 18: ...Project Planning 14 05 01 AWB2700 1384GB WINbloc eco Dimensions 142 mm 90 mm complete 340 g 550 gG 15 ...
Страница 24: ...20 05 01 AWB2700 1384GB ...
Страница 45: ...Wiring Guide 41 05 01 AWB2700 1384GB 3 ZSBE 1 5 25 S PE With one supply for each group of 8 inputs ...
Страница 49: ...Wiring Guide 45 05 01 AWB2700 1384GB 3 ZSBE 1 5 25 2S PE 2 With one supply for each group of 8 inputs ...
Страница 52: ...Mounting Dismounting 48 05 01 AWB2700 1384GB ZSBE 1 5 25 S PE The supplies can be cross connected using a ZQV ...
Страница 62: ...58 05 01 AWB2700 1384GB ...
Страница 73: ...EMC Suitable Wiring 69 05 01 AWB2700 1384GB 5 Figure 26 Routing of potential compensation line and signal line ...
Страница 91: ...Device Data Sets and Type Files 87 05 01 AWB2700 1384GB 9 ...
Страница 109: ...Diagnostic Possibilities with S7 and PB DP 105 05 01 AWB2700 1384GB 9 ...
Страница 120: ...116 05 01 AWB2700 1384GB ...
Страница 146: ...142 05 01 AWB2700 1384GB ...
Страница 150: ...05 01 AWB2700 1384GB 146 ...