Scope of Configuration
61
05/01 AWB2700-1384GB
5
Scope of Configuration
WIN
bloc eco modules can be installed and operated in the most
confined places. The minimum distance to other modules is 10 mm
in all directions in the case of passive components. If the adjacent
components are active (e.g. load circuit supplies, transformers),
then the minimum distance should be at least 75 mm, due to a
temperature increase. However, all ambient temperature data
specified in chapter 10 „Technical Data“ are valid.
Figure 24: Possible minimum distance for passive components
Содержание DP-16DI-ECO
Страница 12: ...8 05 01 AWB2700 1384GB ...
Страница 16: ...12 05 01 AWB2700 1384GB ...
Страница 18: ...Project Planning 14 05 01 AWB2700 1384GB WINbloc eco Dimensions 142 mm 90 mm complete 340 g 550 gG 15 ...
Страница 24: ...20 05 01 AWB2700 1384GB ...
Страница 45: ...Wiring Guide 41 05 01 AWB2700 1384GB 3 ZSBE 1 5 25 S PE With one supply for each group of 8 inputs ...
Страница 49: ...Wiring Guide 45 05 01 AWB2700 1384GB 3 ZSBE 1 5 25 2S PE 2 With one supply for each group of 8 inputs ...
Страница 52: ...Mounting Dismounting 48 05 01 AWB2700 1384GB ZSBE 1 5 25 S PE The supplies can be cross connected using a ZQV ...
Страница 62: ...58 05 01 AWB2700 1384GB ...
Страница 73: ...EMC Suitable Wiring 69 05 01 AWB2700 1384GB 5 Figure 26 Routing of potential compensation line and signal line ...
Страница 91: ...Device Data Sets and Type Files 87 05 01 AWB2700 1384GB 9 ...
Страница 109: ...Diagnostic Possibilities with S7 and PB DP 105 05 01 AWB2700 1384GB 9 ...
Страница 120: ...116 05 01 AWB2700 1384GB ...
Страница 146: ...142 05 01 AWB2700 1384GB ...
Страница 150: ...05 01 AWB2700 1384GB 146 ...