Exchange of Modules
55
Exchange of Modules
After replacement of the modules and connection of the
voltage the configuration button must be pressed. The new
module is assigned an address by this means.
Motor starter or contactor
Device status
The individual SmartWire-Darwin slaves indicate their device
status with the aid of a diagnosis LED.
Table 5:
Diagnostic messages of the SmartWire-Darwin module
for DILM (LED indicator)
j
Danger!
The exchange of the SmartWire-Darwin module for DILM
must only be carried out with the supply switched off.
h
Caution!
The order of the SmartWire-Darwin units must not be
altered.
i
Danger!
The exchange of the motor starter or contactor must only
be carried out after the complete system SmartWire-
Darwin is switched off.
Designation
Colour
State
Message
Ready
Orange
continuous light
Switching command for contactor via
SmartWire-Darwin
Green
continuous light
Device is operating fault-free.
flashing (1 Hz)
• addressing process in progress
– after gateway power On
– after actuation of the
configuration button on the
gateway
• slave not in current configuration
• invalid type