Switching on Contactors DIL-
SWD-32-001, DIL-SWD-32-002
52
Installation
The SmartWire-Darwin modules DIL-SWD-32-001 and DIL-
SWD-32-002 for DILM must be adapted to the
corresponding contactor size prior to installation. The
adjustment required for this is performed by means of the
adjusting slide of the SmartWire-Darwin module for DILM.
X
Set the setting slider on the SmartWire-Darwin module for
the corresponding contactor.
•
Bottom
position: DILA, DILM7, DILM9, DILM12, DILM15
•
Top
position: DILM17, DILM25, DILM32, DILM38
Figure 19: Adjustment of the adjusting slide on
DIL-SWD-32-001 or DIL-SWD-32-002
X
Place the SmartWire-Darwin module for DILM on the
allocated contactor.
h
Caution!
The SmartWire-Darwin module for DILM may be installed
and detached only after the control voltage and supply
cable have been switched off.
Position bottom
Position top