44
TM SmartCool One 5057724 v1.0_08_2022
Technical Data
Operating Temperature Limits
The unit does not offer humidity control and therefore the humidity levels for the unit environment must be controlled by
the customer to ensure a non-latent application.
Minimum
Design
Maximum
°C
°F
°C
°F
°C
°F
Return Air Temperature
28
82.4
36
75.2
45
113.0
Return Air Relative Humidity (%)
9.4%
22.6%
32.7%
Inlet Water Temperature
20
68
28
82.4
36
96.8
Temperature Difference (K /
°R)
6K
10.8°R
8K
14.4°R
12K
21.6 °R
Storage Temperature
Please contact Airedale.