Zeus200
Installation manual
V 1.0.7 - 12/10/2020
Page 22 of 28
2.6.3
Battery type selection
The battery type can be selected using the dip-switches in the power unit, as shown in the following
figure
The
primary battery type (services)
is set using the third and fourth switches, as shown in the
following table.
Position
3
4
Description
@12V
@24V
OFF OFF
Lead
Hermetic/Agm/Gel
(
SEAL
)
Primary
Battery
EE_VEoCBatt1=1
14,2V @25°C 28,4V@25°C
EE_VLB=7
12,2V
23,8V
EE_VELB=6
13,5V
13,5V
EE_Tabs=0
1h
1h
EE_VExitFloat=19
12.5V
25V
ON
OFF
Lead Acid Free
(
FLOOD
)
Primary
battery
EE_VEoCBatt1=0
14,8V @25°C 29,6V@25°C
EE_VLB=7
12,2V
23,8V
EE_VELB=9
14,0V
28,0V
EE_Tabs=0
1h
1h
EE_VExitFloat=19
12.5V
25V
OFF ON
LiFePO4
Primary
battery
EE_VEoCBatt1=6
14,2V
–
no
temperature
compensated
28,4V
–
no
temperature
compensated
EE_VLB=11
12,8V
25,1V
EE_VELB=6
13,5V
27,0V
EE_Tabs=0
1h
1h
EE_VExitFloat=23
12,9V
25,8V
ON
ON
Not allowed:
same settings as
SEAL battery
-
-
Battery type
selection
dip-switches