14
7. PROGRAMMING WHEN USING OWN SIM CARD
If you use your own SIM card, programming is done by SMS commands. In next
sections it is explained how to get in the programming mode and to program by
sending simple SMS text commands to the unit. To learn about the options, please
refer to chapter 5. After programming the units needs to be mounted and tested as
described in chapter 6.
7.1 PROGRAM MODE
A battery-operated Mobeye GSM fire alarm communicator CM2410 switches to the
program mode after placing the batteries. First the GSM module establishes network
connection. During this time the LED flashes green and red. Next it will shortly flash
very fast. Within 10-30 seconds the connection is established and the status LED
starts flashing 1 sec. on/1 sec. off (or stays on continuously in case the first
telephone number has been configured).
During the first 3 minutes, the GSM module remains active, ready to receive SMS
commands. After 3 minutes a time-out occurs and the GSM module switches off in
order to save the batteries. It returns to the program mode by re-inserting the
batteries.
Using external power, the unit is always in program mode.
7.2 PROGRAM AT LEAST ONE TELEPHONE NUMBER
The Mobeye GSM fire alarm communicator CM2410 is able to send messages up to
5 telephone numbers. The first telephone number (TEL1) belongs to the
administrator. Technical messages (such as
battery low
) are sent to the
administrator only. Without the administrator
’s phone number, the Mobeye GSM fire
alarm communicator CM2410 cannot function.
When the GSM fire alarm communicator CM2410 is in initial (factory) status and the
batteries are inserted (so the LED is flashing), the administrator
’s number is
programmed by calling the telephone number of the Mobeye GSM fire alarm
communicator CM2410 using the administrator
’s phone. The unit will recognize this
number and store it as administrator (TEL1). The administrator will receive a
confirmation SMS text message including the security code. This code is needed to
program the other settings in the unit.