EtherCAT
®
Communication Protocol Manual
– p/n 20018109-001 Rev. B
35
To assign 0x1A01 to the TxPOD sync manager
•
Go to EtherCAT PREOP State
•
Write 0x00 to 0x1C13
•
Write 0x1A01 to 0x1C13:01
•
Write 0x01 to 0x1C13
•
Go to EtherCAT SAFEOP State
Similar mapping of Process Control objects (0x4035 and 0x403C) are possible by updating 0x1607 (Hot Cathode
User RxPDO) and/or 0x1A07 (Hot Cathode User TxPDO) with the desired objects, then updating 0x1C12
(RxPDO Assignment) and/or 0x1C13 (TxPDO Assignment).
See ETG.1020 for more information
26
Troubleshooting
Master Reports Slave not Found
Verify Link/Activity LED (see EtherCAT Link/Activity) is flashing indicating a valid physical connection between the
Master and the Slave. If it is not flashing, check wiring including Slave power.
INIT+ERR EtherCAT State with AL Status Code 0x14
“Application” Firmware corrupted. Try re-loading firmware using Firmware Update.
PREOP+ERR EtherCAT State with AL Status Code 0x1D or 0x1E
Verify PDO Configuration is valid
– check if indexes with correct bit-length are mappable.
Pressure is NaN or 0xF383:n Reports “Electronics Failure”
This is most likely due to an internal issue in the electronics
– contact MKS for next steps.
Other Troubleshooting
Contact MKS for support.
27
SDO Abort (Error) Codes
The following is a list of SDO abort codes for when an SDO or CoE communication error occurs. See ETG.1000.6
for more details.
Table 24: SDO Abort Codes
Error Code (hex)
Error code (decimal)
Meaning
05030000
84082688
Toggle bit not changed
05040000
84148224
SDO protocol timeout
05040001
84148225
Client/server command specifier not valid or unknown
05040005
84148229
Out of memory
06010000
100728832
Unsupported access to an object
06010001
100728833
Read access to a write-only object
06010002
100728834
Write access to a read-only object
06010003
100728835
Subindex cannot be written, SI0 must be 0 for write access