Chapter 6: Operation (Profibus Units)
41
User Span / Gas Correction
For tuning the flow controller's accuracy the USER_SPAN parameter should be used and for
application of a specific gas the nominal full scale (e.g. N2) may be multiplied by the GCF of the
gas and the parameter FULL_SCALE_RNG may be set with the result. Another option is to set the
parameter GAS_CORRECTION to the GCF of the gas (full functionality only).
User Zero
The parameter USER_ZERO may be set to the flow sensors offset. (See also
AUTO ZERO
)
Filter
The filter is a single-pole low pass filter. The parameter that the user can adjust is the settling time
of the filter (FILTER_SETTLING). E.g. if a step input (magnitude 100) is applied to the filter with a
settling time of 100 second, the response out of the filter will be within 2% of the final value (98%)
in 100 second. The default value is 0 seconds (no filtering).
Gas Tables
Gas tables may be switched off by setting the default table to 15 (i.e. no table is used) and by
selecting the default table. Or by programming a 0 for POINT_NUM (ref. to
Calibration Table
at
the end of this chapter; function (y=x)) and selecting it. Or by selecting a table with no (zero) points.
A backup of the Gas Tables is generated on Factory Setup. This backup is used for reset the
tables.
Soft Start Rate
A change in the set point is performed in a slope, which is defined by SOFT_START_RATE.
Each controller is factory set to its optimum performance.
Содержание 1579A
Страница 8: ...Table of Contents 1579A 579A viii This page intentionally left blank...
Страница 12: ...Safety Information 1579A 579A 12 This page intentionally left blank...
Страница 16: ...Chapter 1 General Information 1579A 579A 16 This page intentionally left blank...
Страница 20: ...Chapter 2 Shipment 1579A 579A 20 This page intentionally left blank...
Страница 28: ...Chapter 3 Connectors and Control Elements 1579A 579A 28 This page intentionally left blank...
Страница 38: ...Chapter 5 Operation Analog Units 1579A 579A 38 This page intentionally left blank...
Страница 70: ...Chapter 10 Maintenance 1579A 579A 70 This page intentionally left blank...
Страница 74: ...Appendix A Product Specifications 1579A 579A 74 This page intentionally left blank...
Страница 82: ...Appendix C Gas Correction Factors 1579A 579A 82 This page intentionally left blank...
Страница 84: ...Appendix C Gas Correction Factors 1579A 579A 84 This page intentionally left blank...
Страница 86: ...Next page Health and Safety Form Contact MKS at the web or at any MKS location if the form is missing...