43
-
'16 • SCM-T-199
Adapted to
RoHS
directive
Model
Item
FDUM50VF
Power source
1 Phase, 220−240V, 50Hz
Operation data
Cooling
Heating
Nominal capacity (1)
kW
5.0
5.8
Sound power level
dB(A)
60
Sound pressure level
P-Hi : 37 Hi : 32 Me : 29 Lo : 26
Exterior dimensions
Height x Width x Depth
mm
280 × 750 × 635
Exterior appearance
(Munsell color)
—
Net weight
kg
29
Heat exchanger
Louver fin & inner grooved tubing
Air handling equipment
Fan type & Q'ty
Centrifugal fan × 1
Motor <Starting method>
W
100 < Direct line start >
Air flow (Standard)
m
3
/min
P-Hi : 13 Hi : 10 Me : 9 Lo : 8
Available external static pressure
Pa
Standard:35 Max:100
Outside air intake
Possible
Air filter, Q'ty
Procure locally
Shock & vibration absorber
Rubber sleeve(for fan motor)
Remote control
Wired : RC-E5, RC-EX1A (option) Wireless : RCN-KIT3-E (option)
Room temperature control
Thermostat by electronics
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Installation data
Refrigerant piping size
mm
Liquid line: I/U
φ
6.35 (1/4")
Gas line:
φ
12.7 (1/2")
Connecting method
Flare piping
Drain pump
Built-in drain pump
Drain
Hose connectable with VP25
Insulation for piping
Necessary (both Liquid & Gas lines)
IP number
IPX0
Standard accessories
Drain hose
Notes (1) The data are measured at the following conditions.
The pipe length is 7.5m.
Item
Operation
Indoor air temperature
Outdoor air temperature
External static pressure
of indoor unit
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
35Pa
ISO5151-T1
Heating
20˚C
−
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
these values are somewhat higher due to ambient temperature.
(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(5) Static pressure of optional air filter "UM-FL1EF" is 5Pa initially.
(6) If wireless remote control is used, only 3-speed fan setting (Hi-Me-Lo) is availabe.
(6) Duct connected Low/Middle static pressure type (FDUM)
K
PJG000Z159
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...