(C) Current safe control value
Set this using the jumper wire (J1 or J2) on the outdoor PCB. Control starts when it exceeds the control value.
1) Switching with jumper wire
Jumper wire (J2)
Short-circuit
(At shipping from factory)
Short-circuit
Jumper wire (J1)
Short-circuit (At shipping from factory)
Current safe
①
Current safe
②
Open
Current safe
③
Current safe
③
(ii)
(ii)
(i)
(11) Current safe
(a) Purpose
(b) Detail of operation
Cooling
Heating
Lower limit speed
Item
Model
115
SCM40, 45, 50
SCM60, 71, 80
32 rps
32 rps
32 rps
25 rps
SCM100, 125
22 rps
20 rps
2) Control value
Current safe
①
Current safe
②
Current safe
③
Cooling
Heating
Cooling
Heating
Cooling
Heating
10.0
12.0
10.0
10.0
7.5
7.5
Unit: A
(14) Discharge pipe sensor disconnection protection control
(a) When the compressor speed is other than 0 rps.
(i) Tho-D(10)
-
Tho-D(0) < 8 °C, and Tho-D(10)
-
Tho-A(10) < 5 °C
The compressor speed is set on A rps for 5 minutes. After 5 minutes, the compressor speed is set on B rps for 5 minutes.
(ii) Tho-D(20)
-Tho-D(15) < 5 °C
The compressor speed is set on 0 rps.
(b) Once the unit is stopped by this function, it is not restarted.
Notes (1) Tho-D(X): After compressor operation, the discharge pipe temperature sensor after X minutes.
(2) Tho-A(X): After compressor operation, the outdoor air temperature sensor after X minutes.
• Values of A, B
Model
A
B
SCM40ZS-S
SCM45ZS-S
SCM50ZS-S
(12) Current cut
(a) Purpose
(b) Detail of operation
(13) Outdoor unit failure
(23) Indoor fan motor protection
compressor
(SRF:150)
300
-
-
195
-
'16 • SCM-T-199
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...