(ii)
Air flow direction is controlled according to the room temperature and setting temperature.
1) When 3D auto operation starts
2) When Room temp. – Setting temp. is
<=
5ºC during cooling and when setting temp. – Room temp. is
<=
5ºC during
heating, the system switches to the following air flow direction control. After the louver swings left and right sym
-
metrically for 3 cycles, control is switched to the control in 3).
3) After the flap swings for 5 cycles, control is switched to the control in 4).
4) For 5 minutes, the following air flow direction control is carried out.
5) After 5 minutes have passed, the air flow direction is determined according to the room temperature and setting tem
-
perature.
(b)
During DRY operation (including auto DRY operation)
Flap
Louver
Cooling
Up/down swing
Heating
Wide (fixed)
Center (fixed)
Flap
Louver
Cooling
Heating
Left/right swing
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Flap
Louver
Cooling
Up/down swing
Heating
Center (Fixed)
Wide (Fixed)
Flap
Louver
Cooling
Heating
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Operation mode
Room temp. – Setting temp. 2°C
Setting temp. – Room temp. 2°C
Heating
Cooling
Air flow direction contorol
2°C < Setting temp. – Room temp. 5°C
2°C < Room temp. – Setting temp. 5°C
Room temp. – Setting temp. > 5°C
Setting temp. – Room temp. > 5°C
The control in 4) continues.
Control returns to the control in 2).
Control returns to the control in 1).
The control in 4) continues.
Control returns to the control in 2).
Control returns to the control in 1).
<
=
<
=
<
=
<
=
Wide (Fixed)
Flap
Louver
Horizontal blowing (Fixed)
(b) Sleep timer operation
Pressing the SLEEP button causes the temperature to be controlled with respect to the set temperature.
(a) Comfortable timer setting (ON timer)
(c) OFF timer operation
The OFF timer can be set at a specific time (in 10-minute units) within a 24-hour period.
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto
mode operation is selected, the comfortable timer starts and determines the starting time of next operation based on the ini-
tial value of 15 minutes and the relationship between the room temperature at the setting time and the setting temp
erature.
(10) Timer operation
(d) Weekly timer operation
Timer operation (ON timer, OFF timer) can be set up to 4 times a day for each weekday.
(11) Night setback operation
As “Night setback” signal is received from the wireless remote control, the heating operation starts with the setting temperature
at 10
℃
.
-
143
-
'16 • SCM-T-199
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...