7 SCHEDULED MAINTENANCE
Mitsubishi Diesel Engine S16R & S16R2 OPERATION & MAINTENANCE MANUAL
120
Pub. No. K29001-00320 Revision: 1
Rating Definition
*1: This condition constitutes a part of required conditions for warranty that Shanghai MHI Engine co., Ltd. (hereinafter “SME”) agrees
with the other party under Diesel Engine Sales Contract with the party (hereinafter “Individual Contract”), however details of the
warranty descriptions and the conditions shall be referred to the Individual Contract.
Atmospheric condition as per ISO 15550:2002 (JIS B 8003:2005) (Barometic pressure:100 kPa, ambient temperature:298 K,
relative humidity:30%).
*2: Average load factor (per day or year) shall be calculated as per the formula in ISO 8528:2005 ‘average power output (Ppp)’.
*3: Refer to Operation Manual for more information regarding inspection and maintenance including items and descriptions.
*4: Warranty aren’t valid after Major Overhaul.
*5: For backup or emergency purpose engine, it is needed to have output margin of 5% or more for the customer demand output to
avoid engine stall by output tolerance (ISO 15550) and frequency variation etc.
This document may be changed without prior notification.
Table 7-1 SME Generator Use Diesel Engine Rating Definition (1/2)
Symbol
E
P
Name of rating
Critical Power Operation Stand-by
Prime
Limited
Running Time
Unlimited
Running Time
Overload operation (Rack set)
Not possible (E) (*5)
Not possible (E)
+10% (E)
Definition
Applications where there
standby output continu-
ous operation request of
300hr or lower.
Typically example: For
Data center.
Rated power of an emer-
gency generator that sup-
plies power in case of a
failure of main power
source or commercial
power.
Regular power source of
which the operating hour
is limited to the short peri-
od as specified in the re-
quired conditions for
warranty in this docu-
ment.
This rating shall be used
for applications that re-
quire overload operation
with Stand-by.
LTP as specified in ISO
8528:2005.
For generators with vari-
able load and unlimited
operating hour.
PRP (Prime Power) as
specified in ISO
8528:2005.
Required conditions for warranty (*1)
Load/operating time (*2)
Ave. load factor/24 Hr -
80% or lower
(100% in emergency)
Overload (
≤
110%)
: allowed for 1Hr per 12Hr.
80% or lower
·Overload operation
(
≤
110%) is allowed for
1Hr per 12Hr.
·>90% load is allowed for
max. 3Hr per 24Hr opera-
tion.
Ave. load factor/yr
100% or lower
60% or lower
As per
ISO 8528:2005. 100% or
lower
60% or lower
Operating Hr/yr (*4)
Unlimited
500Hr or lower
As per
ISO 8528:2005 500Hr or
lower
Unlimited
Overhaul interval after delivery
<Maximum> (*3)
Top
4 yr
(Only the case exceed
500Hr by 4yr)
4 yr
4 yr
4000Hr or 4yr whichever
comes earlier
Major
600Hr or 8yr whichever
comes earlier
3000Hr or 8yr whichever
comes earlier
1000Hr or 8yr whichever
comes earlier
8000Hr or 8yr whichever
comes earlier
Application
Emergency, stand-by
Seasonal peak cut
Daily peak cut, portable
generator