3 OPERATION
Mitsubishi Diesel Engine S16R & S16R2 OPERATION & MAINTENANCE MANUAL
103
Pub. No. K29001-00320 Revision: 1
Stopping
Be sure to stop the engine as per the operating
guidelines of the generator.
1
Operate the stop switch of the
generator
Devices Installed during
Manufacturing the Generator" (
• If the engine will not stop, perform an
emergency stop by means of the
manual stop lever of the
Checking After Stopping
Check that a fuel, oil or coolant leak from any part
of the engine is not found after the engine is
stopped.
• In case of an unallocated defective
point or leakage, contact your SME
Maintenance Operation
In order to ensure performance of the engine,
perform maintenance operation regularly, in case
that both of the engines for continuous use and
emergency use will not be used for a long time.
• For the generator set of emergency
use, maintenance operation and/or the
report according to the Electric
Utilities Industry Law, Fire Services
Law, or Building Standard Law etc. is
obliged according to the generator set
application.
• The method of inspection and
maintenance, and maintenance
operation differs according to the
device. Contact the device supplier.
■
Once a Week
Operate the engine for 5 to 10 minutes at no load
and check the following points:
• Startability, exhaust color
• Abnormal vibration, noise and odor
• Indication of various instruments (oil pressure
gauge, water temperature gauge, oil temperature
gauge, exhaust temperature gauge, tachometer,
etc.)
• If any abnormality is found, refer to
and correct the defect.
■
Once a Month
Operate the engine at least for 30 minutes at 50%
load or more and check the following points:
• Startability, exhaust color
• Abnormal vibration, noise and odor
• Indication of various instruments (oil pressure
gauge, water temperature gauge, oil temperature
gauge, exhaust temperature gauge, tachometer,
etc.)
• Fuel injection pump and governor rack
movement
• Damper temperature and external view
• If any abnormality is found, refer to
and correct the defect.
Do not restart the engine immediately
after an abnormal stop.
* Investigate the cause of abnormality, correct
the defect, then restart the engine.
Do not race the engine immediately
before shutting it down.
* Otherwise, the devices could be damaged.