10
DEDICATED INSTRUCTIONS
10.4 ZP.UINI
10
- 28
9
P
R
OGRAM
M
ING
10
D
E
DICA
TED
INSTRUC
TI
ONS
11
TR
O
U
BLE
S
HOOTING
A
P
P
E
NDICE
S
INDE
X
(b) Communication speed/transmission setting
Set a speed of communication with the target device and transmission details.
1) Transmission setting
* 1 Set it to OFF (8 bits) in RTU mode.
Figure 10.17 Structure of communication speed and transmission settings
Table10.18 Transmission setting
Bit
Item
OFF(0)
ON(1)
Description
b0
Not used
Fixed to OFF(0)
-
b1
Data bit
*1
8
7
Set data bits.
b2
Parity bit presence
Present
Not present
Specify whether parity bit is present or not.
In the case of "Present", vertical parity check is performed.
b3
Even/odd parity
Even
Odd
Set even or odd parity.
This setting is valid only when "Parity bit presence" is set to
"Present".
b4
Stop bit
1
2
Set the stop bit.
b5
Frame mode
RTU mode
ASCII mode
Set the frame mode.(
b6
Online change
Disable
Enable
Set whether to enable or disable data writing to the RUN-status
programmable controller CPU by a request message from the
master.
If this is set to "Disable", when a message requesting the device
write is received from the master, the QJ71MB91 returns an error
response.
This setting is valid only when the slave function is set for the
channel.
b7
Not used
Fixed to OFF(0)
-
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
Communication speed setting
Transmission setting
b15 b14 b13 b12 b11 b10