10.1 Troubleshooting Flow
10.1.7 Transient transmission is disabled
10
- 9
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
10
TROUBLESHOOTING
10.1.7
Transient transmission is disabled
The following flowchart shows the procedures to be taken when transient transmission is
disabled.
Figure 10.8 When transient transmission is disabled
Transient transmission is disabled.
Is D LINK LED of own or
another station ON or flashing?
ON/flashing
"0"
What is control data completion status?
OFF
"Other
than 0"
Incorrect
Failed
Completed normally
Correct
Test result?
Are Target station's CPU type,
Target network No. and Target station No.
in control data correct?
Perform [Communication test] in GX Developer.
Check the sequence program of other stations
(for overwriting of data).
Check the error details by the error code and take
corrective actions.
Modify the control data.
Modify routing parameters.
End
Relevant bit ON
(Baton pass
error station)
Relevant bit OFF
(Normal baton pass station)
Baton pass status of each station
(SW00A0 to SW00A7)
Connect GX Developer to another station.
Check error factors in CC IE Control Network
Diagnostics, and take corrective actions according
to the troubleshooting section.
ON
(Station No.
not set)
OFF (Station No. set)
Station No. setting status
(own station) (SB0070)
Using the UINI instruction, set station No.
CHAPTER 9 DEDICATED INSTRUCTIONS
Section 6.8 Routing Parameters
Section 5.7.1 Communication test
Section 10.1.4 D LINK LED is OFF
Section 10.4 Checking the Error Description
with the CC IE Control Network Diagnostics
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......