9
- 174
9.20 J(P)/G(P).RIWT
9
DEDICATED INSTRUCTIONS
9.20 J(P)/G(P).RIWT
This instruction writes the specified points of data to the target station's device.
(1) Setting data
* 1 Local devices and file registers for each program cannot be used as devices used in setting data.
Table 9.108 Devices available for setting data
Setting
data
Available devices
Internal device
(System, User)
File
register
Link direct device
J
\
Intelligent
function
module device
U
\
G
Index
register Zn
Constant
Others
Bit
Word
Bit
Word
K,H
$
(S1)
—
—
(S2)
—
—
(D)
—
Figure 9.151 Instruction format
Table 9.109 Setting data
Setting data
*1
Description
Data type
Jn
Network number of the own station (1 to 239, 254)
254: The network specified in Valid module during other station access
Binary 16 bits
Un
Start I/O number of the own station's CC-Link IE controller network
module
(00 to FE
H
: The higher two digits of the 3-digit I/O number)
(S1)
Start device of the own station that stores control data.
(
(2) Control data in this section)
Device name
(S2)
The own station's start device where write data are stored.
(D)
The own station's device that is turned on for one scan upon
completion of the instruction.
(D) + 1 also turns on if the instruction execution has failed.
Bit
J.RIWT
JP.RIWT
J.RIWT
JP.RIWT
G.RIWT
GP.RIWT
G.RIWT
GP.RIWT
Start contact
[Instruction format]
[Execution
condition]
[Instruction
symbol]
Start contact
Jn
(S1)
(S2)
(D)
Jn
(S1)
(S2)
(D)
Un
(S1)
(S2)
(D)
Un
(S1)
(S2)
(D)
Start contact
Start contact