2
- 1
2.1 CC-Link IE Controller Network Configurations
2.1.1 Single network system
2
SYSTEM CONFIGURATION
CHAPTER2 SYSTEM CONFIGURATION
This chapter describes system configurations for the CC-Link IE controller network
module.
2.1
CC-Link IE Controller Network Configurations
2.1.1
Single network system
The single network system is a system that consists of a control station and normal
stations, which are connected with optical fiber cables.
* 1 A personal computer equipped with a CC-Link IE controller network interface board can be
connected as a control or normal station of the CC-Link IE controller network.
For details on the CC-Link IE controller network interface board, refer to the following manual.
CC-Link IE controller network interface board User's Manual
* 2 By connecting a CC-Link IE controller network module to a GOT, the GOT can be connected to the
CC-Link IE controller network as a normal station.
For details on the CC-Link IE controller network communication unit, refer to the following manual.
GT15 User's Manual
POINT
One network (of the same network No.) cannot contain both CC-Link IE controller
network and MELSECNET/H modules. (Different networks must be used.)
• CC-Link IE controller network module: Used for CC-Link IE controller
network
• MELSECNET/H module: Used for MELSECNET/H or MELSECNET/10
Figure 2.1 Single network system
Control station
Station No.1
CC-Link IE controller network
interface board
*1
Normal station
Station No.2
Normal station
Station No.120
Normal station
Station No.3
CC-Link IE controller
network module
CC-Link IE controller network
communication unit
*2
Optical fiber cable