4 - 9 4 - 9
MELSEC-Q
4 SETUP AND PROCEDURE BEFORE OPERATION
Switch No.
Setting items
Setting details/bit assignment
Default value
Switch 3
Input filter setting
(CH1 to CH4)
CH1 Input filter 0:30kpps
1:10kpps
2:1kpps
3:100pps
4:50pps
5:10pps
6:1pps
7:0.1pps
CH2 Input filter
CH3 Input filter
CH4 Input filter
H
Setting items
Meaning
0000
H
Switch 4
Input filter setting
(CH5 to CH8)
CH5 Input filter
0:30kpps
1:10kpps
2:1kpps
3:100pps
4:50pps
5:10pps
6:1pps
7:0.1pps
CH6 Input filter
CH7 Input filter
CH8 Input filter
H
Setting items
Meaning
0000
H
Switch 5
Vacant
(1) Input voltage selection (Switch 1: lower 8 bits)
Set the level of the input signal on each channel.
(2) Pulse edge selection (Switch 2: lower 8 bits)
Set the pulse edge (rise edge/fall edge) on each channel.
For pulse edge selection, the differences between the rise edge and fall edge
and the count timings are shown below.
1) Rise edge
Count number
Pulse input
1
2
3
4
5
6
2) Fall edge
Pulse input
Count number
1
2
3
4
5
6
(3) Linear counter or Ring counter selection (Switch 2: upper 8 bits)
Set the count type (linear counter or ring counter) on each channel. (Refer to
Section 5.2.)
(4) Input filter setting (Switch 3, Switch 4)
Set the input pulse counting speed (maximum) on each channel. (Refer to
Section 3.1.)
Содержание QD60P8-G
Страница 1: ......
Страница 2: ......
Страница 6: ...A 4 A 4 Disposal Precautions CAUTION When disposing of the product handle it as industrial waste ...
Страница 14: ...A 12 A 12 MEMO ...
Страница 18: ...1 4 1 4 MELSEC Q 1 OVERVIEW MEMO ...
Страница 95: ...7 12 7 12 MELSEC Q 7 PROGRAMMING MEMO ...
Страница 115: ...9 7 9 7 MELSEC Q 9 TROUBLESHOOTING MEMO ...
Страница 121: ...App 2 App 2 MELSEC Q APPENDIX MEMO App ...
Страница 124: ...Index 3 Index 3 MEMO ...
Страница 127: ......
Страница 128: ......