3 - 14 3 - 14
MELSEC-Q
3 SPECIFICATIONS
3.5 Interface with External Devices
The internal circuit of the QD60P8-G interface for connection of external devices is
shown in a schematic diagram.
Input/
Output
Internal circuit
Terminal
number
Signal name
Operation
Input voltage
(guaranteed
value)
Operating current
(guaranteed
value)
5VDC *
3.5V to 5.5V
4mA or more
1, 3, 5, 7,
9, 11,
13, 15
CH1 to 8 V+ At ON
12 to 24VDC *
10.2 to 30V
4mA or more
5VDC *
1.0V or less
0.5mA or less
Input
2, 4, 6, 8,
10, 12,
14, 16
CH1 to 8 V- At OFF
12 to 24VDC *
2.0V or less
0.5mA or less
- -
17
18
FG - -
-
*: Use the intelligent function module switch to change between 5VDC and 12 to 24VDC.
(For details, refer to "Section 4.5 Switch setting for intelligent function module".)
Signal layout of each channel
Terminal number
Signal name
1 CH1
V+
CH1
2 CH1
V-
3 CH2
V+
CH2
4 CH2
V-
5 CH3
V+
CH3
6 CH3
V-
7 CH4
V+
CH4
8 CH4
V-
9 CH5
V+
CH5
10 CH5
V-
11 CH6
V+
CH6
12 CH6
V-
13 CH7
V+
CH7
14 CH7
V-
15 CH8
V+
CH8
16 CH8
V-
Содержание QD60P8-G
Страница 1: ......
Страница 2: ......
Страница 6: ...A 4 A 4 Disposal Precautions CAUTION When disposing of the product handle it as industrial waste ...
Страница 14: ...A 12 A 12 MEMO ...
Страница 18: ...1 4 1 4 MELSEC Q 1 OVERVIEW MEMO ...
Страница 95: ...7 12 7 12 MELSEC Q 7 PROGRAMMING MEMO ...
Страница 115: ...9 7 9 7 MELSEC Q 9 TROUBLESHOOTING MEMO ...
Страница 121: ...App 2 App 2 MELSEC Q APPENDIX MEMO App ...
Страница 124: ...Index 3 Index 3 MEMO ...
Страница 127: ......
Страница 128: ......