5.3 Intelligent Function Module Switch Settings
(1) Setting item
Intelligent function module switch has switches 1 to 5.The setting is
executed with 16-bit data.
When not setting the intelligent function module switch, the default
of switches 1 to 5 is 0.
*1 Setting any value within the setting range will provide the same operation.
When the setting range is 1 to F
H
, set 1 for example.
*2 Setting a value other than "0" results in an error.
Table 5.1 Intelligent function module switch settings
Setting item
Switch 1
Thermocouple type
settings
(CH1 to CH4)
When setting a value other than 0 to 7 , a
thermocouple type settings error 10 []( [] indicates
target channel number.) occurs and a temperature
conversion is not performed.
Switch 2
Thermocouple type
settings
(CH5 to CH8)
Switch 3
Offset/gain setting mode
Switch 4
Switch 5
0 : Fixed *2
CH4 CH3 CH2 CH1
H
Thermocouple type
Setting value
Thermocouple K
0
Thermocouple E
1
Thermocouple J
2
Thermocouple T
3
Thermocouple B
4
Thermocouple R
5
Thermocouple S
6
Thermocouple N
7
CH8 CH7 CH6 CH5
H
0: Factory default setting
1: User range setting
H
0
0
b7
b6
b5
b4
b3
b2
b1
b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
Fixed to 0
H
: Normal mode
: Offset/gain setting mode
: With cold junction temperature compensation
: Without cold junction temperature compensation
H
Fixed to 0
0
H
1 to F
H
*1
0
H
1 to F
H
*1
0
0