6

 

 4. Handling Precautions 

 

 

(1) Do not drop the module case or subject it to heavy impact. 
(2) Do not remove the PCB of the module from its case. Doing so may cause 

the module to fail. 

(3) Be careful not to let foreign particles such as swarf or wire chips enter the 

module. They may cause a fire, mechanical failure or malfunction. 

(4) The top surface of the module is covered with a protective film to prevent 

foreign objects such as wire burrs from entering the module during wiring. 
Do not remove this film until the wiring is complete. Before operating the 
system, be sure to remove the film to provide adequate heat ventilation. 

(5) Tighten the screws such as module fixing screws within the following 

ranges. 
Loose screws may cause short circuits, failures, or malfunctions. 

 

Screw location 

Tightening torque 

range 

Module fixing screw (M3 screw) 

*1

 

0.36 to 0.48 N·m 

Terminal block screw (M3 screw) 

0.42 to 0.58 N·m 

Terminal block mounting screw (M3.5 screw) 

0.66 to 0.89 N·m 

FG terminal screw (M3 screw) 

*2

 

0.42 to 0.58 N·m 

*1: The module can be easily fixed onto the base unit using the hook at the 

top of the module. 
However, it is recommended to secure the module with the module 
fixing screw if the module is subject to significant vibration. 

*2: Q68DAVN, Q68DAIN only 

 

 5. Wiring 

 

 

5.1 Wiring precautions 

In order to optimize the functions of the D/A converter module and ensure system 
reliability, external wiring that is protected from noise is required. 
Please observe the following precautions for external wiring: 
 

(1) Use separate cables for the AC control circuit and the external input signals 

of the D/A converter module to avoid the influence of the AC side surges 
and inductions. 

 

(2) Do not mount the cables close to or bundle them with the main circuit line, a 

high-voltage cable or a load cable from other than the programmable 
controller. This may increase the effects of noise, surges and induction. 

 

(3) Perform a one-point grounding for shielded lines and the shields of sealed 

cables. 

 

(4) A solderless terminal with insulating sleeve cannot be used for the terminal 

block. Covering the cable- connection portion of the solderless terminal 
with a marked tube or an insulation tube is recommended. 

Содержание Q62DAN

Страница 1: ... Thank you for purchasing the Mitsubishi general purpose programmable controller MELSEC Q Series Prior to use please read this manual thoroughly and familiarize yourself with the product MODEL Q D A N U H W MODEL CODE 13JP80 IB NA 0800321 C 0808 MEE 2005 MITSUBISHI ELECTRIC CORPORATION ...

Страница 2: ...se hazardous conditions resulting in medium or slight personal injury or physical damage Note that the CAUTION level may lead to a serious consequence according to the circumstances Always follow the instructions of both levels because they are important to personal safety Please save this manual to make it accessible when required and always forward it to the end user Design Precautions CAUTION z...

Страница 3: ...ule with the fixing hole as a supporting point Incorrect loading of the module can cause a malfunction failure or drop When using the programmable controller in the environment of much vibration tighten the module with a screw z Tighten the screw in the specified torque range Undertightening can cause a drop short circuit or malfunction Overtightening can cause a drop short circuit or malfunction ...

Страница 4: ...al cover could result in electric shock z Tighten the terminal screws with the specified torque If the terminal screws are loose it could result in short circuits fire or erroneous operation Tightening the terminal screws too far may cause damages to the screws and or the module resulting in fallout short circuits or malfunction z Be sure there are no foreign substances such as sawdust or wiring d...

Страница 5: ...321 C Correction Compliance with the EMC and Low Voltage Directives Chapter 4 This manual confers no industrial property rights or any rights of any other kind nor dose it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual 2005 MITSUBISHI E...

Страница 6: ...Configurator DA SW2D5C QDAU E SH 080054 13JR02 Compliance with the EMC and Low Voltage Directives 1 For programmable controller system To configure a system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi programmable controller EMC and Low Voltage Directives compliant into other machinery or equipment refer to Chapter 9 EMC AND LOW VOLTAGE DIRECTIV...

Страница 7: ...he Q68DAVN Q68DAIN type digital analog converter module hereinafter referred to as the Q68DAIN In this manual the Q62DAN Q64DAN Q68DAVN and Q68DAIN are collectively referred to as the D A Digital Analog converter modules After unpacking confirm that the following products are enclosed Model code Product name Quantity Q62DAN Q62DAN Model Digital Analog Converter module 1 Q64DAN Q64DAN Model Digital...

Страница 8: ...lution mode High resolution mode Analog output range Digital input value Maximum resolution Digital input value Maximum resolution 0 to 5V 1 25 mV 0 416 mV 1 to 5V 0 to 4000 1 0 mV 0 to 12000 0 333 mV 10 to 10V 2 5 mV 16000 to 16000 0 625 mV Voltage User range setting 4000 to 4000 0 75 mV 12000 to 12000 0 333 mV 0 to 20 mA 5 A 1 66 A 4 to 20 mA 0 to 4000 4 A 0 to 12000 1 33 A Current User range se...

Страница 9: ...er and analog output 500VDC 20M or more 500VDC 20M or more I O occupied points 16 points I O assignment Intelligent 16 points Connected terminals 18 points terminal block Applicable wire size 0 3 to 0 75 mm2 Applicable solderless terminal R1 25 3 A solderless terminal with sleeve cannot be used FG terminal R1 25 3 1 25 YS3 RAV1 25 3 V1 25 YS3A Other terminals than FG R1 25 3 A solderless terminal ...

Страница 10: ...nt V 14 Vacant COM 15 Vacant CH4 I 16 24 V 17 24 G ERROR IN 24VDC RUN Q6 DAN FG 0 20mA D A 10 10V 18 17 16 15 14 13 12 11 10 9 8 5 6 7 4 1 2 3 1 2 3 18 FG Signal name Terminal number Q68DAVN Q68DAIN 1 V I 2 CH1 COM CH1 COM 3 V I 4 CH2 COM CH2 COM 5 V I 6 CH3 COM CH3 COM 7 V I 8 CH4 COM CH4 COM 9 V I 10 CH5 COM CH5 COM 11 V I 12 CH6 COM CH6 COM 13 V I 14 CH7 COM CH7 COM 15 V I 16 CH8 COM CH8 COM 17...

Страница 11: ...rror occurred or online module change enabled 2 ERROR LED Displays the error status of the D A converter module On Error Off Normal operation Flashing Error in switch settings Switch No 5 of the intelligent function module has been set to a value other than 0 3 External power supply terminal This is the terminal for connecting the 24 V DC external power supply 4 FG terminal Frame ground terminal ...

Страница 12: ... 0 42 to 0 58 N m 1 The module can be easily fixed onto the base unit using the hook at the top of the module However it is recommended to secure the module with the module fixing screw if the module is subject to significant vibration 2 Q68DAVN Q68DAIN only 5 Wiring 5 1 Wiring precautions In order to optimize the functions of the D A converter module and ensure system reliability external wiring ...

Страница 13: ...ut 1 kΩ 1 MΩ D A conversion V COM 1 2 Motor drive module etc GND DC DC converter 24V 24G FG 24 V DC Filter to b For current output 0Ω 600Ω D A conversion I COM 1 2 Motor drive module etc GND DC DC converter 24V 24G FG 24 V DC Filter to 1 Use a twisted two core shielded wire for the power wire 2 If there is noise or ripples in the external wiring connect a 0 1 to 0 47 F25V capacitor between the V I...

Страница 14: ...C Filter to 3 For Q68DAIN 0Ω 600Ω D A conversion I COM 1 2 Motor drive module etc GND DC DC converter 24V 24G FG 24 V DC Filter to 1 Use a twisted two core shielded wire for the power wire 2 If there is noise or ripples in the external wiring connect a 0 1 to 0 47 F25V capacitor between the V I terminal and COM ...

Страница 15: ...5 to CH8 H CH8CH7CH6CH5 For Q62DAN and Q64DAN H CH4CH3CH2CH1 HOLD CLEAR function setting 0H CLEAR 1 to FH numeric value other than 0H HOLD Switch 3 For Q68DAVN and Q68DAIN CH8CH7CH6CH5CH4CH3CH2CH1 b7 b6 b5 b4 b3 b2 b1 b0 b8 0 b15 0 to HOLD CLEAR function setting 0 CLEAR 1 HOLD Switch 4 H 00H 01 to FFH numeric value other than 00H Normal mode non synchronized Synchronized output mode 0H 1 to FH num...

Страница 16: ...ng mode is set using intelligent function module switch 4 other settings by switch 4 settings for resolution mode and synchronous output mode will be ignored 5 Perform the offset gain settings after checking the RUN LED flashes in offset gain setting mode If the RUN LED does not flash check to see if the switch 4 setting is correct 6 Since the analog output value will differ considerably depending...

Страница 17: ... 08 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 112 4 41 Unit mm inch 2 Q64DAN 90 3 54 98 3 86 27 4 1 08 112 4 41 Q64DAN RUN IN 24VDC ERROR 9 8 5 6 7 4 1 2 3 18 17 16 15 14 13 12 11 10 C H 1 I V COM C H 2 I V COM C H 3 I V COM C H 4 I V COM FG 0 20mA D A 10 10V Unit mm inch ...

Страница 18: ...tal fitting Accessory 0 37 Unit mm inch 4 Q68DAIN 90 3 54 98 3 86 9 5 112 4 41 27 4 1 08 FG ERROR RUN Q68DAIN C H 8 C H 7 C H 6 C H 5 C H 4 C H 3 C H 2 I C O M I C O M I C O M I C O M I I C O M C O M C H 1 C O M I I C O M I N 24VD C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 M3 screw Accessory M3 screw Accessory 63 2 48 71 5 2 81 FG terminal L Shaped metal fitting Accessory 0 37 Unit mm inch ...

Страница 19: ...13 MEMO ...

Страница 20: ...es Barcelona Spain Tel 34 93 565 3131 France Mitsubishi Electric Europe B V French Branch 25 Boulevard des Bouvets F 92741 Nanterre Cedex France TEL 33 1 5568 5568 South Africa Circuit Breaker Industries Ltd Private Bag 2016 ZA 1600 Isando South Africa Tel 27 11 928 2000 Hong Kong Mitsubishi Electric Automation Hong Kong Ltd 10th Floor Manulife Tower 169 Electric Road North Point Hong Kong Tel 852...

Отзывы: