8.3 Replacing Module in Redundant System
8.3.4 I/O Module Replacement Procedure
8
8.3.4 I/O Module Replacement Procedure
(1) Module Replacement during Power OFF
When replacing the control system I/O module, switch its system to standby system,
power off the standby system, and then start the replacement operation.
System switching is not necessary when replacing the standby system I/O module.
Make sure to power off the standby system before replacing the I/O module.
The standby system can be powered off while the redundant system is running.
(2) Module Replacement during Power ON
By using the online module change of GX Developer, the I/O module can be replaced
while the redundant system is running, regardless of its system, i.e., control system or
standby system.
POINT
The I/O modules of control system and standby system cannot perform online
module change (hot swapping) using GX Developer when connecting the
extension base unit to the CPU module whose first 5 digits of serial No. is 09012
or later.
When replacing modules online using GX Developer in other than above cases,
refer to the following manual.
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
Diagram 8.26 I/O Module Replacement System during Power OFF
Diagram 8.27 I/O Module Replacement System during Power ON
Control system
Standby system
Tracking cable
Replace after turning OFF
the standby system power.
I/O module
GX Developer
Control system
Standby system
Tracking cable
I/O module
Replace after using GX Developer to
switch over to the standby system.
GX Developer