5.1 Basic Concept of Redundant System
5.1.4 System Consistency Check
5
REDUNDANT SYSTEM FUNCTIONS
Consistency Check Target, – Out of Consistency Check Target
* 1 The consistency check is executed only in the following cases:
•After online program change is completed (the consistency check is executed only for the
program files.)
•At system switching
(The consistency check is executed under the above conditions only.)
* 2 The consistency check is not executed under any other conditions not listed in the table.
* 3 "Unreset" indicates that the RESET/L.CLR switch is set to the neutral position.
Remark
The consistency check will not be executed during the following:
• Memory copy from control system to standby system
Table5.10 Consistency Check Execution Conditions between System A and System B
Conditions *1
Description
Execution
Timing
Operation
Mode
Standby
System
Operating
Status
Control
System
Operating
Status
File
Operating
Status
Basic System
Configuration
Memory Card
Settings
Parameter
Valid Drive
Settings
Execution Timing
Operation Mode
Standby System
Operating
Status
Control System
Operating
Status
File
Operating
Status
Basic System
Configuration
Memory Card
Settings
Parameter Valid
Drive Settings
Both systems
powered on
simultaneously
Backup Mode
–
–
Both systems
Unreset
*3
simultaneously
Backup Mode
–
–
END processing
Backup Mode
RUN
RUN
*
1
–
–
–
STOP
PAUSE
–
–
–
–
STOP
RUN
–
–
–
STOP
PAUSE
RUN
STOP
PAUSE
–
–
–
–
STOP
RUN
–
–
–
–
STOP
RUN
RUN
–
–
–
STOP
PAUSE
–
–
–
–
Power ON
Unreset
*3
RUN
–
STOP
PAUSE
–
–
Changing from
Separate Mode
to Backup Mode
RUN
STOP
RUN
Power ON
Unreset
*3
RUN
–
STOP
PAUSE
–
–
Tracking cable
reconnected
Backup Mode
RUN
RUN
–
STOP
PAUSE
RUN
STOP
PAUSE
–
–