Appendix 2 Special Register List
APPENDICES
*3: This applies to Universal model QCPUs except for the QnUDE(H)CPU.
*4: This applies to the following modules.
• Q02UCPU, Q03UDCPU, Q04UDHCPU, Q06UDHCPU that the first 5 digits of the serial No. is "10012" or higher.
• Q13UDHCPU, Q26UDHCPU, QnUDE(H)CPU
Number
Name
Meaning
Explanation
Set by
(When Set)
Corres-
ponding
ACPU
D9
Corresponding
CPU
SD100
Transmission
speed storage
area
Stores the
transmission
speed specified in
the serial
communication
setting.
96
: 9.6kbps,
192
: 19.2kbps,
384 : 38.4kbps,
576 : 57.6kbps,
1152 : 115.2kbps
S (Power-ON or
reset)
New
Q00/Q01
SD101
Communication
setting storage
area
Stores the
communication
setting specified in
the serial
communication
setting.
* : Since the data is used by the system, it is undefined.
S (Power-ON or
reset)
New
SD102
Transmission
wait time
storage area
Stores the
transmission wait
time specifed in
the serial
communication
setting.
0
: No waiting time
1 to F
H
: Waiting time (unit: 10ms)
Defaults to 0.
S (Power-ON or
reset)
New
SD105
CH1
transmission
speed setting
(RS-232)
Stores the preset
transmission
speed when GX
Developer is
used.
96
: 9600bps,
192
: 19.2kbps,
384
: 38.4kbps,
576 : 57.6kbps,
1152 : 115.2kbps
*: Other than RS-232 connection holds the data at RS-232 connection.
(When disconnected, the default value is 1152.)
S
New
Qn(H)
QnPH
QnPRH
QnU
*3
Rem
SD110
Data sending
result storage
area
Stores the data
sending result
when the serial
communication
function is used.
Stores the error code at the timeout sending data.
S (Error)
New
Q00/Q01
SD111
Data receiving
result storage
area
Stores the data
receiving result
when the serial
communication
function is used.
Stores the error code at the time of receiving data.
S (Error)
SD118
Amount of
battery
consumption
Amount of battery
consumption
Displays current amount of battery consumption.
Range: 1 to 2 (Q02UCPU, Q03UDCPU, Q04UDHCPU,
Q03UDECPU, Q04UDEHCPU)
1 to 3 (Q06UDHCPU, Q06UDEHCPU)
1 to 4 (Q13UDHCPU, Q26UDHCPU,
Q13UDEHCPU, Q26UDEHCPU)
S (Status
change)
New
QnU
*4
SD119
Battery life-
prolonging
factor
Battery life-
prolonging factor
Stores the factor which makes the battery life-prolonging function valid.
When SD119 is other than 0, the battery life-prolonging function is valid.
S (Status
change)
New
QnU
b0
to
b3
b4
b5
b6
b15
to
Sumcheck yes/no
0: Present
1: Absent
0: Disabled
1: Enabled
Online program correction setting
b0: CPU switch setting
0:No factor
1:Foctor
b1: Backup in execution by
latch data backup function
(to standard ROM)
b15
to
b2 b1 b0