Appendix 1 Special Relay List
APPENDICES
(16)Redundant power supply module information
*1: The "power supply 1" indicates the redundant power supply module (Q64RP) mounted on the POWER 1 slot of the redundant base unit (Q38RB/Q68RB/
Q65WRB).
The "power supply 2" indicates the redundant power supply module (Q64RP) mounted on the POWER 2 slot of the redundant base unit (Q38RB/Q68RB/
Q65WRB).
*2: The module whose first 5 digits of serial No. is "04012" or later.
However, for the multiple CPU system configuration, this applies to all CPU modules whose first 5 digits of serial No. are "07032" or later.
Number
Name
Meaning
Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM1760
Transfer trigger
completion flag
OFF : Transmission
uncompleted
ON
: Transmission end
SM1760
Block 49
<In the case of Q4AR>
Turns ON only during one
scan when the transmission
of the corresponding data is
completed.
<In the case of QnPRH>
Turns ON only during one
scan when the transmission
of the corresponding block is
completed.
S (status change)
New
Q4AR
QnPRH
SM1761
SM1761
Block 50
SM1762
SM1762
Block 51
SM1763
SM1763
Block 52
SM1764
SM1764
Block 53
SM1765
SM1765
Block 54
SM1766
SM1766
Block 55
SM1767
SM1767
Block 56
SM1768
SM1768
Block 57
SM1769
SM1769
Block 58
SM1770
SM1770
Block 59
SM1771
SM1771
Block 60
SM1772
SM1772
Block 61
SM1773
SM1773
Block 62
SM1774
SM1774
Block 63
SM1775
SM1775
Block 64
TableApp.17 Special relay
Number
Name
Meaning
Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM1780
Power supply off
detection flag
OFF : No redundant power
supply module with
input power OFF
detected
ON : Redundant power
supply module with
input power OFF
detected
• Turns ON when one or more redundant power
supply modules with input power OFF are detected.
• Turns on if any of SD1780 bits is on.
• Turns off if all bits of SD1780 are off.
• Turns OFF when the main base unit is not the
redundant main base unit (Q38RB).
0: communication with peripheral device is executed
1: communication with peripheral device is
nonexecuted
S (Each END)
New
Qn(H)*2
QnPH*2
QnPRH
Rem
SM1781
Power supply failure
detection flag
OFF : No faulty redundant
power supply module
detected
ON : Faulty redundant
power supply module
detected
• Turns ON when one or more faulty redundant power
supply modules are detected.
• Turns on if any of SD1781 bits is on.
• Turns off if all bits of SD1781 are off.
• Turns OFF when the main base unit is not the
redundant main base unit (Q38RB).
0: communication with peripheral device is executed
1: communication with peripheral device is
nonexecuted
S (Each END)
SM1782
Momentary power
failure detection flag
for power supply 1 *1
OFF : No momentary power
failure detected
ON : Momentary power
failure detected
• Turns ON when a momentary power failure of the
input power supply to the power supply 1 or 2 is
detected one or more times. After turning ON,
remains ON even if the power supply recovers from
the momentary power failure.
• Turns OFF the flag (SM1782, SM1783) of the power
supply 1/2 when the CPU module starts.
• When the input power to one of the redundant power
supply modules turns OFF the corresponding flag
turns OFF.
• Turns OFF when the main base unit is not the
redundant main base unit (Q38RB).
0: communication with peripheral device is executed
1: communication with peripheral device is
nonexecuted
S (Each END)
SM1783
Momentary power
failure detection flag
for power supply 2 *1