10.2.11 Counter (C)
(c) Setting the interrupt counter
In order to use interrupt counters, set Interrupt counter start No. at the "PLC
system" tab screen in the "(PLC) Parameter" dialog box.
The number of points indicated in Table10.8 starting from the set counter number
is used as interrupt counters.
In order to use an interrupt counter, an "interruption permitted" status must be
established by E1 instruction at the main routine program.
Table10.8 Number of interrupt counter points of each CPU module
Basic model QCPU
High Performance model QCPU,
Process CPU, Redundant CPU
128 points, starting from the set counter number, are
used as interrupt counters.
When the first interrupt counter No. is set to C300,
C300 to 427 are used as interrupt counters.
256 points, starting from the set counter number, are used as
interrupt counters.
When the first interrupt counter No. is set to C300, C300 to 555
are used as interrupt counters.
I0
I1
I2
I127
C300
C301
C302
C427
Values corresponding to
the interrupt counter No.
Interrupt counter (128 points)
I0
I1
I2
I255
C300
C301
C302
C555
Interrupt counter (256 points)
Values corresponding to
the interrupt counter No.
Содержание Q00CPU