9
- 10
9.1 PLC Parameters
9.1.1 Basic model QCPU
9
PARAMETERS
Table9.8 I/O assignment list (Continued)
Item
Parameter No.
Description
Setting range
Default value
Reference
Basic
setting
Base
model
name
0401
H
Set the model name of the used
main base unit or extension base
unit. (User memo. Not used for
the CPU module.)
16 characters
No setting
Power
model
name
Set the model name of the
power supply module mounted
on the main base unit or
extension base unit. (User
memo. Not used for the CPU
module.)
16 characters
No setting
Extension
cable
Set the extension cable model
name. (User memo. Not used for
the CPU module.)
16 characters
No setting
Slots
Set the number of slots of the
main base unit or extension base
unit.
Set the number of slots for all
base units.
2,3,5,8,10,12
No setting
Switch setting
0407
H
Set various switches of the
intelligent function module.
Refer to the manual of the used
intelligent function module.
No setting
Detail
setting
Error time
output
mode
0403
H
Set whether the output will be
cleared or held when the control
CPU results in a stop error.
Clear/Hold
Clear
Hardware
error time
PLC
operation
mode
4004
H
Set whether the control CPU will
stop or continue operation when
the hardware fault of the
intelligent function module
occurs.
Stop/Continue
Stop
I/O
response
time
0405
H
Set the response time of the
input module, high-speed input
module, hybrid I/O module or
interrupt module.
• Input, hybrid I/O : 1ms, 5ms,
10ms, 20ms, 70ms
• High-speed input, interrupt :
0.1ms, 0.2ms, 0.4ms, 0.6ms,
1ms
Input, hybrid I/O :
10ms
High-speed input,
interrupt : 0.2ms
Control
PLC
0406
H
Set the control CPU of the I/O
module and intelligent function
module.
• No. 1, No. 2, No. 3
No. 1
QCPU User's Manual
(Multiple CPU
System)
Содержание Q00CPU
Страница 1: ......
Страница 2: ......
Страница 972: ...Index 6 Memo ...
Страница 975: ......
Страница 976: ......