6
- 190
6.25 Service Processing
6.25.2 Service processing
6
FUNCTIONS
(2) Parameter setting
The service processing can be set in the PLC system tab of the PLC parameter dialog
box.
The service processing can be executed by selecting one of the parameter items in
Table6.59. Setting values for non-selected parameter items cannot be entered.
(Default: Execute the process as the scan time proceeds. =10%)
Figure 6.110 Parameter setting screen
Table6.59 Parameter item list
Item name
Description
Setting range
Remarks
Execute the process as the
scan time proceeds.
Specifies the percentage of service
processing for one scan.
• Range: 1 to 99%
• Unit: 1%
Default at selection =10%
Specify service process time.
Specifies the time of service processing
for one scan.
• Range: 0.2ms to 1000ms
• Unit: 0.1ms
Default at selection
=0.2ms
Specify service process
execution counts.
Specifies the count of service processing
for one scan.
• Range: 1 to 10 times
• Unit: 1 time
Default at selection
=1 time
Execute it while waiting for
constant scan setting.
Specifies whether to execute the service
processing while waiting for constant scan
setting.
------
Even when the waiting
time is 0.2ms or less, the
service processing time
(0.2ms) will be added to
the scan time at service
processing execution.