6
FUNCTIONS
6.22 High Speed Interrupt Function
6.22.4 Restrictions
6
- 175
1
O
verv
iew
2
Per
fo
rma
nce
S
p
ecifica
tio
n
3
S
equ
en
ce P
ro
g
ra
m
Co
nfig
ura
tio
n a
nd
E
xecut
io
n Co
nd
iti
o
ns
4
I/O N
unb
er
Assig
n
m
e
nt
5
Me
mor
ie
s a
nd
File
s
Ha
nd
led
by CP
U Mo
du
le
6
Func
tions
7
Co
mmu
nic
a
tion
us
in
g
bu
ilt
-i
n E
th
e
rne
t po
rt
s o
f
CP
U mod
u
le
8
Co
mm
un
icatio
n
w
ith
Int
e
lli
ge
nt
Fun
ction
Mo
du
le
6.22.4 Restrictions
Note79Note80
This section provides the cautions when executing the high speed interrupt function and
the restrictions.
Depending on the cautions, an WDT error may occur, or high speed interrupt may not be
executed at preset cycle intervals.
The items are classified into 4 types depending on the restriction level.
(1) Items that are completely disabled.
(2) Items that are restricted on the high speed interrupt.
(3) Items that have priority over the high speed interrupt when interrupt is disabled.
(4) Items other than (1) to (3)
The time taken to run an interrupt program once should not exceed the preset time of the
interrupt cycle interval. (Make sure the time required for an interrupt program once is
within the preset time of the interrupt cycle interval. Otherwise, high speed interrupt
operation cannot be guaranteed.)
(1) Items that are completely disabled
Note79
Note80
Table6.48 Items that are completely disabled
No.
Item
Restriction
When Used
1
CPU module
Only the CPU modules listed in Section 6.22 (1)
support the high speed interrupt function.
Parameter error is detected.
2
Base unit
QA1S6 B or QA6 B base unit is not
available.
Parameter error is detected.
3
Multiple CPU system
Multiple CPU system is not available.
Checked at parameter setting of GX Developer.
4
Instruction
PR/PRC, UDCNT1/2, PLSY, PWM, SPD,
PLOADP/PUNLOADP/PSWAPP instructions are
not available.
Any of the instructions indicated on the left is not available and error is
detected.
5
Instruction
Instruction that will take longer processing time
than high speed interrupt cycle is not available.
Since interrupt is disabled during instruction execution, high speed
interrupt is not available at preset cycle.
6
Programming unit
Programming unit is not available.
Response to instruction search will be slow, or communication error
may occur on programming unit side.
7
SFC
The following two SFC functions are not
available.
• SFC transition monitor check function using
SM90 to SM99, SD90 to SD99
• Fixed-time executed block execution function
Functions given on the left are not available and are ignored.
8
Sampling trace
Time-based sampling trace is not
available.(Sampling trace can be used every
scan or when detailed conditions are executed.)
Sampling trace is not executed (it is ignored).
(When reading the trace data, the trace results may not be displayed.)
Basic
Process
Redundant
UD
Universal
Note6.77
High
Performance
Note6.78
The Basic model QCPU, Process CPU, Redundant CPU, and Universal model QCPU do not
support the high speed interrupt function.
Basic
Process
Redundant
UD
Universal
The Q02CPU does not support the high speed interrupt function.
Check the versions of CPU module and GX Developer when using the high speed interrupt
function in the QnHCPU. (