OPERATING PROCEDURE
PHOTOS
90
12. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 2 cover panel (front) fixing screws (5 × 12) and
remove the front cover panel. (See Photo 2-1)
(4) Remove 2 cover panel (rear) fixing screws (5 × 12) and
remove the back cover panel.
(5) Remove the electrical parts box. (See Photo 3)
(6) Remove the valve bed. (Refer to procedure 8)
(7) Remove the side panel (R). (Refer to procedure 8)
(8) Remove 2 separator fixing screws (4 × 10) and remove the
separator.
(9) Remove the soundproof cover for compressor.
(10) Recover refrigerant.
(11) Remove the welded pipe of compressor inlet and outlet
then remove the compressor.
(12) Remove the 3 points of the compressor fixing nut using a
spanner or a adjustable wrench.
Note: Recover refrigerant without spreading it in the air.
13. Removing the power receiver
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the cover panel (front). (Refer to procedure 12)
(4) Remove the cover panel (rear). (Refer to procedure 12)
(5) Remove the electrical parts box. (See Photo 3)
(6) Remove the valve bed. (Refer to procedure 8)
(7) Remove the side panel (R). (Refer to procedure 8)
(8) Recover refrigerant.
(9) Remove 4 welded pipes of power receiver inlet and outlet.
(10) Remove 2 receiver leg fixing screws (4 × 10).
(See Photo 10)
Note: Recover refrigerant without spreading it in the air.
Photo 10
Receiver leg
fixing screws
Receiver leg
Photo 11
Power
receiver
Compressor
Valve bed
Separator
fixing screw
Separator
Compressor
fixing nuts
Valve bed
fixing
screws
Valve bed
fixing screw
11. Removing the reactor (ACL)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical parts box. (See Photo 3)
(4) Remove 4 reactor fixing screws (4 × 20) and remove the
reactor.
Note: The reactor is attached to the rear of the electrical parts
box.
Reactor fixing screws
Photo 9
Electrical parts box
Reactor fixing screws
Reactor
(ACL)
Power receiver
Inlet
Outlet
OCH533D