80
CHAPTER 7
VARIOUS SETTINGS
This chapter describes the setting procedures of the high-speed counter module.
7.1
Parameter Setting
Set the parameter of this module with the network parameter written to the CPU module of the master station. When
the setting in GX Works2 and the parameter written to the CPU module do not match, the parameter cannot be read
and written. For the setting procedure of the master station, refer to the following.
User's manual for the master/local module used
Write and read the parameter setting of this module with the CPU module in the STOP status.
(Writing and reading are unavailable in the RUN status.)
Remark
●
When points less than the ones of the high-speed counter module and extension module are set for the remote I/O signal
and remote register, no error occurs. The cyclic transmission is performed for the data of the points set from the start.
●
When using the high-speed counter module, do not invalidate Block Data Assurance per Station on the "CC IE Field
Supplementary Setting" window.
For the block data assurance per station, refer to the following.
User's manual for the master/local module used
●
Do not set the parameter using the CCPASET instruction in the master station. Correct operation of the high-speed
counter module cannot be guaranteed because the module operates with the block data assurance per station disabled
when the CCPASET instruction is executed.
Do not uncheck the box.
Содержание NZ2GFCF-D62PD2
Страница 1: ......
Страница 2: ......
Страница 54: ...52 Memo ...
Страница 206: ...204 Memo ...
Страница 303: ......
Страница 304: ......