270
(7) Module-based parameter data (address: 0122
H
to 0123
H
, 0142
H
to 0143
H
)
Address
Name
Description
Default
CH1
CH2
0122
H
0142
H
Pulse input mode
• Set the pulse input mode.
• The following shows the setting range.
0: 1-Phase Multiple of 1
1: 1-Phase Multiple of 2
2: CW/CCW
3: 2-Phase Multiple of 1
4: 2-Phase Multiple of 2
5: 2-Phase Multiple of 4
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned off then on
0
0123
H
0143
H
Counting speed
setting
• Set the counting speed.
• The following shows the setting range.
0: 10kpps
1: 100kpps
2: 200kpps
3: 500kpps
4: 1Mpps
5: 2Mpps
6: 4Mpps
7: 8Mpps
• Always set 200kpps or slower to the counting speed when DC input is used
for connecting.
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned off then on
0