45
CHAPTER 6 INSTALLATION AND WIRING
6
6.1 Station Nu
mber Setting
CHAPTER 6
INSTALLATION AND WIRING
This chapter describes the installation and wiring of the D/A converter module.
6.1
Station Number Setting
(1) Setting procedure
Set the station number with the rotary switch on the front of the module. The setting value of the station number
becomes valid when the module is powered on. Thus, set the station number when the module is powered off.
• The hundreds and tens places of the station number are set with x10.
• The ones place of the station number is set with x1.
Ex.
To set the station number to 115, set the switch as shown below.
(2) Setting range
Set the station number from 1 to 120. Setting the value other than 1 to 120 causes a communication error and the
D LINK LED flashes.
●
Changing the station number setting switch while the module is powered on causes a minor error and flashes the ERR.
LED.
Returning the station number setting switches to the previous setting eliminates the error after five seconds and turns off
the ERR. LED.
●
Do not set a station number duplicated with other station numbers. If the station number is duplicated, a communication
error occurs and the D LINK LED does not turn on.
Содержание NZ2GF2B-60DA4
Страница 1: ......
Страница 2: ......
Страница 44: ...42 Memo...
Страница 117: ...115 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo...
Страница 167: ...165 APPENDICES A Appendix 9 External Dimensions Memo...
Страница 173: ......
Страница 174: ......