6 - 23
6 - 23
6. HOW TO COMMUNICATE WITH ID TAGS
6.4.1 Set parameters
The Set Parameters program is a program for setting parameters such as the
communication specification or processing specification.
(1) Program conditions
(a) Parameter setting contents
Intelligent Function
Module Device
Address
Buffer Memory Name
Setting Contents
U0
\
G1
Communication specification
area (CH1)
K0 (Trigger)
U0
\
G2
Processing specification area
(CH1)
K0 (Data storage order:
Upper –> Lower
Calculation method: Addition
Calculation/Verification:
Calculation)
U0
\
G10
Auto command wait time
setting area (CH1)
K0 (Continuously executes the ID
instruction until there is a
response from the ID tag)
U0
\
G11
Processing result monitor
switch setting area (CH1)
K0 [Stores the communication time
in the processing result monitor
storage area (U0
\
G42)]
U0
\
G4001
Communication specification
area (CH2)
K0 (Trigger)
U0
\
G4002
Processing specification area
(CH2)
K0 (Data storage order:
Upper –> Lower
Calculation method: Addition
Calculation/Verification:
Calculation)
U0
\
G4010
Auto command wait time
setting area (CH2)
K0 (Continuously executes the ID
instruction until there is a
response from the ID tag)
U0
\
G4011
Processing result monitor
switch setting area (CH2)
K0 [Stores the communication time
in the processing result monitor
storage area (U0
\
G4042)]
(b) Devices used by user
1. External inputs (commands)
Device Application
M1000
Set parameters command