Appendix 4 Buffer Memory Areas
Input signal error/Disconnection detection automatic clear enable/disable setting
Set whether to enable or disable auto-clear of input signal error or disconnection detection with the input signal error detection
function or disconnection detection function.
Setting a value other than in the table above results in operation with Disable (1).
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is Disable (1) for all the channels.
Offset/gain writing enable code
When the offset/gain initialization request (Un/G70, b5) turns off
→
on by setting the enable code "E20FH" in this area at the
time of initialization of offset/gain, the offset value and the gain value in the flash memory of the multiple input module are
initialized.
When setting anything other than "E20FH" in this area, initialization is not executed.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Default value
The default value is set to 0.
CH1 Digital output value
The converted digital output value is stored in 16-bit signed binary value.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Refreshing cycle
The value is updated every conversion cycle.
Setting value
Description
0
Enable
1
Disable
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Input signal error/Disconnection detection automatic clear
enable/disable setting
304
Input signal error/disconnection detection auto-clear enable/
disable setting (in FX2N allocation mode function)
133
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Offset/gain writing enable code
305
Offset/gain initialization enable code (In FX2N allocation mode
function)
1340
(1) Data section
(2) Sign bit 0: Positive, 1: Negative
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Digital output value
400
600
800
1000
1200
1400
1600
1800
CH
Digital output value (in FX2N allocation mode function)
1001
1003
1005
1007
1009
1011
1013
1015
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
(1)
(2)