5 INSTALLATION
5.5 Connecting Methods for CPU Module and Extension Devices
75
5
Connection of power cables
Power cable connection of the CPU module, extension power supply module and I/O
modules
The power must be supplied to the FX5UC CPU module, FX5-C1PS-5V, FX5-C
EX/D, and FX5-C32ET/D.
Use the power cable for CPU modules to supply the power to the FX5UC CPU module and FX5-C1PS-5V.
To supply the power to FX5-C
EX/D and FX5-C32ET/D, use two power connectors (upper and lower) on each module for
crossover wiring.
FX5-C
EX/DS and FX5-C32ET/DSS do not have power connectors. Supply the power to them using input connectors.
The following products are provided with power cables.
• Wiring FX5-C
EX/D or FX5-C32ET/D to a subsequent stage
Since the two power connectors on each module of FX5-C
EX/D and FX5-C32ET/D are connected in parallel inside the
module, they have no difference and can be either an inlet port or outlet port for supplying the power. Thus, cables can be
connected to either of the connectors.
However, since the lower connector is covered with a resin cover at shipment from the factory, use the upper connector
preferentially. Remove the resin cover only when crossover wiring to a subsequent module is performed.
(FX5-C
EX/DS and FX5-C32ET/DSS do not have power connectors and the power is supplied from using input connectors.
Thus, removing the resin cover is not required.)
Precautions
To perform crossover wiring, supply the power from the preceding module to the subsequent module. The power cannot be
supplied from the subsequent module to the preceding module.
Classification
Application
Model
Length
Provided with
A
Power cable for CPU modules, extension power supply
module
FX2NC-100MPCB
1 m
FX5UC-
MT/D, FX5UC-
MT/DSS,
FX5-C1PS-5V
B
Power cable for FX5-C
EX/D and FX5-C32ET/D
FX2NC-100BPCB
1 m
FX5UC-
MT/D
C
Power crossover cable for FX5-C
EX/D and FX5-C32ET/D
FX2NC-10BPCB1
0.1 m
FX5-C
EX/D, FX5-C32ET/D
3: Ground (Green)
1: (Red)
FX5UC CPU module,
FX5-C1PS-5V
The following shows the pin numbers of the power connectors.
2: (Black)
1: (Red)
2: (Black)
CPU module
Input module (extension connector type)
Output module (extension connector type)
Input/output module (extension connector type)
Resin cover
Since the lower connector is covered with a resin cover at
shipment from the factory, use the upper connector
preferentially. Remove the resin cover only when crossover
wiring to a subsequent extension module is performed.
FX5-C
EX/D,
FX5-C32ET/D
Crossover wiring between input
extension blocks
Green: Ground
Black:
Red:
Red:
Black:
Содержание MELSEC iQ-F FX5UC