2 SPECIFICATIONS
2.2 Power Supply Specifications
21
2
■
Expansion adapter
For information concerning the dielectric withstand voltage and insulation resistance of each expansion adapter, refer to
manuals of each expansion adapter.
■
Intelligent function module
For information concerning dielectric withstand voltage and insulation resistance of each intelligent function module, refer to
manuals of each intelligent function module.
2.2
Power Supply Specifications
The CPU module power supply specifications are explained below.
For the consumption current of each extension module, refer to
Page 31 PRODUCT LIST or manuals of each extension
module.
DC power supply
*1 This item shows value when only the CPU module is used.
The value in [] is the value in the maximum configuration connectable to the CPU module. (The value does not include the external 24 V
DC power supply of extension devices)
The following shows the power failure detection time of the FX5UC CPU module.
Item
Specifications
Power supply voltage
24 V DC
Voltage fluctuation range
+20%, -15%
Allowable instantaneous power failure time
Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
Power fuse
125 V, 3.15 A Time-lag fuse
Rush current
FX5UC-32MT/
35 A max. 0.5 ms or less/24 V DC
FX5UC-64MT/
FX5UC-96MT/
40 A max. 0.5 ms or less/24 V DC
Power consumption
FX5UC-32MT/
5 W/24 V DC [30 W/24 V DC +20%, -15%]
FX5UC-64MT/
8 W/24 V DC [33 W/24 V DC +20%, -15%]
FX5UC-96MT/
11 W/24 V DC [36 W/24 V DC +20%, -15%]
24 V DC power supply capacity
500 mA
5 V DC power supply capacity
720 mA
1 scan time
Power failure
detection time
SD8008
5 ms
Approx.
2 ms
DC power supply
SM8000:
SM8007:
SM8008:
RUN monitor
Momentary
power failure
detection
Power failure
detected
Содержание MELSEC iQ-F FX5UC
Страница 1: ...MELSEC iQ F FX5UC User s Manual Hardware ...
Страница 2: ......
Страница 15: ...13 CONTENTS ...
Страница 183: ......