162
APPX
Appendix 7 Terminal Module
Output specifications
■
Relay output (FX-16EYR-TB, FX-16EYR-ES-TB/UL)
Item
Specifications
Output type
Relay
External voltage
250 V AC or less, 30 V DC or less
Max. load
Resistance load
2 A/point
The total load current per common terminals (four points) should be 8 A or less.
Inductive load
80 VA
Min. load
5 V DC, 2 mA (reference values)
Open circuit leakage current
Response time
Approx. 10 ms
ON voltage of output element
1.5 V
Insulation of circuit
Mechanical insulation
Indication of output operation
LED is lit when the power is supplied to relay coils.
Power consumption
1.92 W (80 mA 24 V DC)
Input/output configuration circuit
FX-16EYR-TB
FX-16EYR-ES-TB/UL
Unsupported applications
Positioning, Pulse Y Output ((D)PLSY) instruction, Pulse Width Modulation ((D)PWM) instruction,
ABS Current Value Read (DABS) instruction, Start/stop of high-speed I/O function ((D)HIOEN)
instruction, Input Matrix (MTR) instruction, Digital Switch (DSW) instruction, Seven Segment With
Latch (SEGL) instruction
0 to 7
COMn
External wiring
LED
24 V DC 5 mA
Fuse
24+
CN1
connector
side
0 to 7
COMn
External wiring
LED
24 V DC 5 mA
Fuse
24-
CN1
connector
side
Содержание MELSEC iQ-F FX5UC
Страница 1: ...MELSEC iQ F FX5UC User s Manual Hardware ...
Страница 2: ......
Страница 15: ...13 CONTENTS ...
Страница 183: ......