9 -
11
9.
ERROR CODE LIST
9.4
Error Code List for the AnACPU and A3A Board
Table 9.3 shows the error messages, error codes, description and cause of error and
corrective actions of detailed error codes.
Error codes, detailed error codes and error steps are stored in the following special
registers.
Error code:
D9008
Detailed error code: D9091
Error step:
D9010 and D9011
Table 9.3 Error Code List for AnACPU and A3A Board
Error Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
"INSTRCT
CODE ERR."
(Checked when
STOP
RUN
or at execution
of instruction.)
10
101
STOP
Instruction codes which the CPU
cannot decode are included in the
program.
(1) Read the error step using a
peripheral device and correct the
program of the step.
(2) Check the ROM if it contains
instruction codes which cannot be
decoded. If it does, replace it with a
correct ROM.
102
Index qualification is specified for a 32-
bit constant.
Read the error step using a peripheral
device and correct the program of the
step.
103
Device specified by a dedicated
instruction is not correct.
104
An dedicated instruction has incorrect
program structure.
105
An dedicated instruction has incorrect
command name.
106
Index qualification using Z or V is
included in the program between
and
.
107
(1) Index qualification is specified for
the device numbers and set values
in the
instruction of timers and
counters.
(2) Index qualification is specified at the
label number of the pointer (P)
provided to the head of destination
of the
,
,
,
,
,
and
instructions or at the
label number of the interrupt pointer
(I) provided to the head of an
interrupt program.
108
Errors other than 101 to 107 mentioned
above.
LEDA/B IX
LEDA/B IXEND
OUT
CJ
SCJ
CALL
CALLP
JMP
LEDA/B FCALL
LEDA/BBREAK
Содержание MELSEC-A series
Страница 1: ......
Страница 2: ......
Страница 13: ...A 11 MEMO...
Страница 505: ...APPENDICES APP 100 MELSEC A MEMO...
Страница 507: ......
Страница 508: ......