1
1. SPECIFICATIONS
1.1 SPECIFICATIONS
*1
This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from
fixed facilities. The surge voltage withstand level for up to the rated voltage of
300V is 2500V.
Table 1.1 General specification
Item
Specifications
Operating
ambient
temperature
0 to 55
°
C
Storage
ambient
temperature
−
20 to 75
°
C
Operating
ambient
humidity
10 to 90%RH, non-condensing
Storage
ambient
humidity
Vibration
resistance*4
Compliant with
JIS B 3502
and IEC
61131-2
Frequency
Constant
acceleration
Half
amplitude
Sweep
count
Under
intermittent
vibration
5 to 9Hz
-
3.5mm
10 times
each in
X, Y, Z
directions
9 to 150Hz
9.8m/s
2
-
Under
continuous
vibration
5 to 9Hz
-
1.75mm
-
9 to 150Hz
4.9m/s
2
-
Shock
resistance
Compliant with JIS B 3502 and IEC 61131-2
(147 m/s
2
, 3 times each in 3 directions X, Y, Z)
Operating
atmosphere
No corrosive gases
Operating
altitude *3
0 to 2000m
Installation
location
Inside a control panel
Overvoltage
category *1
II or less
Pollution
degree *2
2 or less
Equipment
class
Class I