App - 13 App - 13
APPENDIXES
Example) When the local station where expanded cyclic setting has been made and the remote I/O stations
where remote I/O station points setting has been made are connected
Remote I/O station
(Station number 4,
Occupies 1 station,
Remote I/O station point
setting: 8-point setting)
Remote I/O station
(Station number 3,
Occupies 1 station,
Remote I/O station point
setting: 8-point setting)
Master station
Local station
(Station number 1,
Occupies 2 stations,
Expanded cyclic setting:
octuple)
Buffer memory name
Value
Description
Station No. 1 RX offset
4000
H
Head buffer memory address of RX of station No. 1
Station No. 1 RX size
24 (18
H
)
384 (number of RX points) / 16 = 24 words
Station No. 2 RX offset
4000
H
As 2 stations are occupied, the area of station No. 1 is checked.
Station No. 2 RX size
0 (default)
As 2 stations are occupied, the area of station No. 1 is checked.
Station No. 3 RX offset
4018
H
Head buffer memory address of RX of station No. 3
Station No. 3 RX size
1 (1
H
)
Though the lower 8 bits of the buffer memory address 4018
H
are the corresponding size of
RX of station No. 3, 1 is stored since less than 1 word is rounded up.
Station No. 4 RX offset
4018
H
Head buffer memory address of RX of station No. 4
Station No. 4 RX size
1 (1
H
)
Though the upper 8 bits of the buffer memory address 4018
H
are the corresponding size of
RX of station No. 4, 1 is stored since less than 1 word is rounded up.
Station No. 1 RY offset
4200
H
Head buffer memory address of RY of station No. 1
Station No. 1 RY size
24 (18
H
)
384 (number of RY points) / 16 = 24 words
Station No. 2 RY offset
4000
H
As 2 stations are occupied, the area of station No. 1 is checked.
Station No. 2 RY size
0 (default)
As 2 stations are occupied, the area of station No. 1 is checked.
Station No. 3 RY offset
4218
H
Head buffer memory address of RY of station No. 3
Station No. 3 RY size
1 (1
H
)
Though the lower 8 bits of the buffer memory address 4218
H
are the corresponding size of
RY of station No. 3, 1 is stored since less than 1 word is rounded up.
Station No. 4 RY offset
4218
H
Head buffer memory address of RY of station No. 4
Station No. 4 RY size
1 (18
H
)
Though the upper 8 bits of the buffer memory address 4218
H
are the corresponding size of
RY of station No. 4, 1 is stored since less than 1 word is rounded up.
Station No. 1 RWw offset
4400
H
Head buffer memory address of RWw of station No. 1
Station No. 1 RWw size
64 (40
H
)
2 (number of occupied stations) 32 (expanded cyclic setting) = 64
Station No. 2 RWw offset
4400
H
As 2 stations are occupied, the area of station No. 1 is checked.
Station No. 2 RWw size
0 (default)
As 2 stations are occupied, the area of station No. 1 is checked.
Station No. 3 RWw offset
4440
H
Head buffer memory address of RWw of station No. 3
Station No. 3 RWw size
0 (default)
Buffer memory size of RWw of station No. 3
Station No. 4 RWw offset
4440
H
Head buffer memory address of RWw of station No. 4
Station No. 4 RWw size
0 (default)
Buffer memory size of RWw of station No. 4
Station No. 1 RWr offset
4C00
H
Head buffer memory address of RWr of station No. 1
Station No. 1 RWr size
64 (40
H
)
2 (number of occupied stations) 32 (expanded cyclic setting) = 64
Station No. 2 RWr offset
4C00
H
As 2 stations are occupied, the area of station No. 1 is checked.
Station No. 2 RWr size
0 (default)
As 2 stations are occupied, the area of station No. 1 is checked.
Station No. 3 RWr offset
4C40
H
Head buffer memory address of RWr of station No. 3
Station No. 3 RWr size
0 (default)
Buffer memory size of RWr of station No. 3
Station No. 4 RWr offset
4C40
H
Head buffer memory address of RWr of station No. 4
Station No. 4 RWr size
0 (default)
Buffer memory size of RWr of station No. 4
Содержание L26CPU-BT
Страница 1: ......
Страница 2: ......
Страница 7: ...A 5 A 5 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Страница 32: ...3 5 3 5 3 SPECIFICATIONS ...
Страница 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Страница 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Страница 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Страница 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Страница 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Страница 139: ...8 33 8 33 8 FUNCTIONS ...
Страница 151: ...8 45 8 45 8 FUNCTIONS ...
Страница 243: ...11 6 11 6 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS Set parameters as follows ...
Страница 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Страница 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Страница 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Страница 324: ...15 3 15 3 15 TROUBLESHOOTING 1 When the master station RUN LED is off 2 Common module check procedure ...
Страница 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Страница 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Страница 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Страница 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Страница 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Страница 439: ...App 75 App 75 APPENDIXES MEMO ...
Страница 447: ......
Страница 448: ......
Страница 449: ......