2 - 2 2 - 2
2 PART NAMES
Number Name
Description
The data link status can be checked with each ON/OFF status.
LED name
Description
RUN
On : Operating normally
Off : Watchdog timer error
L RUN
On: Data link is being executed
MST
On: Operating as a master station. (in data link control)
S MST
On: Operating as a standby master station. (in standby status)
SD
On: Data being sent
RD
On: Data being received
ERR.
On: All stations have a communication error
This LED also turns on when the following errors occur.
There are more than one master station on the same line.
There is an error in the parameter settings.
The data link monitoring timer was activated.
The cable is disconnected.
The transmission path is affected by noise.
To check the source of the error, refer to Section 15.3.
Or, refer to Appendix 3.2 for details on SW0058 (detailed LED
display status).
Flashing: A communication error station identified, or remote
station No. duplicated.
L ERR.
On : Communication error (host)
Flashing: The terminating resistor is not attached. The module or
CC-Link Ver.1.10 compatible cable is affected by
noise.
B RATE
On : Operating at the indicated transmission speed.
All off: Transmission speed auto following up
(When succeeded, the LED of the followed transmission
speed turns on.)
1) LED
indicators
STATION
NO.
The module station number setting is indicated.
<Range>
Master station : 0 (All off)
Local station and standby master station : 1 to 64
(Example) When the station number 15 is indicated
: On
: Off
10 5
10
+
5 = 15
2
Содержание L26CPU-BT
Страница 1: ......
Страница 2: ......
Страница 7: ...A 5 A 5 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Страница 32: ...3 5 3 5 3 SPECIFICATIONS ...
Страница 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Страница 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Страница 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Страница 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Страница 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Страница 139: ...8 33 8 33 8 FUNCTIONS ...
Страница 151: ...8 45 8 45 8 FUNCTIONS ...
Страница 243: ...11 6 11 6 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS Set parameters as follows ...
Страница 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Страница 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Страница 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Страница 324: ...15 3 15 3 15 TROUBLESHOOTING 1 When the master station RUN LED is off 2 Common module check procedure ...
Страница 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Страница 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Страница 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Страница 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Страница 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Страница 439: ...App 75 App 75 APPENDIXES MEMO ...
Страница 447: ......
Страница 448: ......
Страница 449: ......