9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
9 - 43
C
O
NN
ECTION T
O
RK
C TEMPE
R
A
T
UR
E CON
T
R
O
LLER
9
Unit address settings
Set the unit address using the unit address setting
switch.
9.5.3
Connecting to Z-TIO, Z-DIO,
Z-CT
(1) Communication settings
Make the communication settings of the temperature
controller.
*1
Adjust the settings with GOT settings.
*2
Select the module address without overlapping with that of
other units.
(2) Setting DIP switches
Make the settings of transmission speed, data bit
configuration, communication protocol
Unit address setting switch
Setting range: 0 to F
Item
Setting range
Communication speed
*1
9600bps, 19200bps, 38400bps
Communication protocol
MODBUS
Data bit configuration
Data bit : 8bits, Parity : None
Data bit : 8bits, Parity : Even
Data bit : 8bits, Parity : Odd
Stop bit : 1bit (fixed)
Unit address
*2
0 to F
Interval time
0 to 250ms
Setting item
Set value
Switch position
1
2
3
4
5
6
Communication
speed
9600bps
ON
OFF
19200bps
OFF
ON
38400bps
ON
ON
Data bit
configuration
Data bit: 8bits,
Parity: None
OFF OFF
ON
Data bit: 8bits,
Parity: Even
OFF
ON
ON
Data bit: 8bits,
Parity: Odd
ON
ON
ON
Communication
protocol
MODBUS
ON
12345678
ON
OFF ON
Front side
Right side
Dip switch
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......