8 - 30
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.5 Temperature Controller Side Setting
8.5.2
Connecting to UT100 Series
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
8.5.3
Connecting to UT2000 Series
Communication settings
Make the communication settings using setting
switches.
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other
units.
Settings by switch
(1) Settings of the transmission speed and the parity
Make those settings by operating the communication
setting Rotary switch.
(2) Communication mode settings
Make this setting by operating the communication
mode select DIP SW.
(3) A setting of the station No.
Make this setting by operating the station No. select
Rotary switch.
8.5.4
Connecting to UTAdvanced
Series
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
Item
Set value
Transmission speed
9600bps
Data bit
*1
7bits, 8bits
Parity bit
*1
Even, odd, none
Stop bit
*1
1bit, 2bits
Address
*1*2
1 to 99
Protocol selection
*1
0: PC link communication (without sum check)
1: PC link communication (with sum check)
Item
Set value
Transmission speed
9600bps
Data bit
*1
8bits (fixed)
Parity bit
*1
Even, odd, none
Stop bit
*1
1bit (fixed)
Station No.
*1*2
1 to 16
Communication mode
PC link communication mode
Switch position
Transmission
speed
Parity bit
0
9600bps
None
1
Odd
2
Even
Communication mode
select DIP SW
Communication setting
Rotary switch
Station No. select
Rotary switch
A
B C D E
F
0
1
2 3
4
5
6
7
8
9
Switch position
Communication mode
ON
PC link communication mode
Switch position
Station No.
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
A
11
B
12
C
13
D
14
E
15
F
16
Item
Set value
Transmission speed
*1
9600bps, 19200bps, 38400bps
Data bit
*1
7bits, 8bits
Parity bit
*1
Even, odd, none
Stop bit
*1
1bit, 2bits
Address
*1*2
1 to 99
Minimum response time
*1
0 to 10 (x 10ms)
Protocol selection
*1
0: PC link communication (without sum check)
1: PC link communication (with sum check)
ON
OFF
A
B C D E
F
0
1
2 3
4
5
6
7
8
9
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......