12 - 12
12. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
12.4 PLC Side Setting
12.4 PLC Side Setting
The GOT operates as the stations of which are shown
below in the CC-Link system.
The switch settings and parameter settings of the PLC side
(CC-Link module) are described in 12.4.1 to 12.4.7.
HINT
HINT
HINT
Number of stations occupied
The number of stations occupied is setting for
determining number of link device points (RX/RY/
RWw/RWr) used by the GOT.
To use multiple numbers of link device points in the
case of cyclic transmission between the GOT and CC-
Link module, set the number of stations occupied as
the exclusive station 4.
The number of link device points at the exclusive
station 1 and 4 is shown below.
CC-Link Ver.2
CC-Link Ver.1
Station data
Description
Station type
Intelligent device station, Ver.1 intelligent device
station or Ver.2 intelligent device station
Number of stations
occupied
Station 1 or Station 4
Model name
Refer to
CC-Link
module
(Q Series)
Connecting
with
Ver.1
compatible
QJ61BT11,
QJ61BT11N
Connecting
with Ver.2
compatible
QJ61BT11N
Connecting
with Ver.1/
Ver.2
compatibles
mixed
QJ61BT11N
CC-Link module
(QnA Series)
AJ61QBT11,
A1SJ61QBT11
CC-Link module
(A Series)
AJ61BT11,
A1SJ61BT11
Link
device
Expanded cyclic setting
Single
Double
Quadruple
Octuple
Exclu
sive
statio
n 1
Exclu
sive
statio
n 4
Exclu
sive
statio
n 1
Exclu
sive
statio
n 4
Exclu
sive
statio
n 1
Exclu
sive
statio
n 4
Exclu
sive
statio
n 1
Exclu
sive
statio
n 4
Remote
input (RX)
32
points
128
points
32
points
224
points
64
points
448
points
128
points
896
points
Remote
output (RY)
32
points
128
points
32
points
224
points
64
points
448
points
128
points
896
points
Remote
register
(RWw)
4
points
16
points
8
points
32
points
16
points
64
points
32
points
128
points
Remote
register
(RWr)
4
points
16
points
8
points
32
points
16
points
64
points
32
points
128
points
Link device
Number of stations occupied
Exclusive station
Exclusive station 4
Remote input (RX)
32 points
128 points
Remote output (RY)
32 points
128 points
Remote register (RWw)
4 points
16 points
Remote register (RWr)
4 points
16 points
Содержание GOT2000 Series
Страница 2: ......
Страница 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 64: ......
Страница 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Страница 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Страница 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Страница 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Страница 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Страница 416: ......
Страница 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Страница 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Страница 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Страница 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Страница 542: ......
Страница 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Страница 568: ......
Страница 592: ...19 24 19 MULTI CHANNEL FUNCTION 19 3 GOT Side Settings Example Setting example for Ethernet connection 4 channels ...
Страница 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Страница 600: ......
Страница 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Страница 670: ...REVISIONS 2 ...
Страница 673: ......