5 - 36
5. ETHERNET CONNECTION
5.4 PLC Side Setting
(3) Communication confirmation
The RDY LED on the Ethernet module turn on when
the module is ready to communicate.
For confirming the communication state, refer to the
following.
■
Confirming the communication state of
The BUF1 LED turns on when the opening processing
of the connection No. 1 is completed in normal at
executing of the sequence program example described
at (2).
[Controller Setting] and [Ethernet] of GT
Designer3
(1) Controller setting
(2) GOT Ethernet setting
(3) Ethernet setting
POINT
POINT
POINT
[Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT
Designer3, refer to the following.
5.3.1 Setting communication interface
(Communication settings)
RUN
BUF1
BUF2
BUF3
BUF4
BUF5
BUF6
BUF7
BUF8
RDY
BSY
SW.ERR.
COM.ERR.
CPU R/W
TEST
TEST ERR.
BSY
SW.ERR.
COM.ERR.
CPU R/W
TEST ERR.
TEST
RDY
RUN
BUF1
BUF2
BUF3
BUF4
BUF5
BUF6
BUF7
BUF8
A1SJ71E71N3-T, A1SJ71E71N-B5,
A1SJ71E71N-B2, A1SJ71E71N-T,
A1SJ71E71N-B5T, A1SJ71E71-B5-S3,
A1SJ71E71-B2-S3
AJ71E71N3-T, AJ71E71N-B5,
AJ71E71N-B2, AJ71E71N-T,
AJ71E71N-B5T, AJ71E71-S3
Item
Set value (Use default value)
GOT Net No.
1
GOT Station
1
GOT Ethernet Setting
192.168.3.18
GOT Communication Port No.
5002
Retry
3times
Startup Time
3sec
Timeout Time
3sec
Delay Time
0ms
Item
Set value (Use default value)
GOT IP Address
192.168.3.18
Subnet Mask
255.255.255.0
Default Gateway
0.0.0.0
Peripheral Communication
Port No.
5015
Transparent Port No.
5014
Item
Set value
Ethernet
setting No.1
Host
*
N/W No.
1
PLC No.
2
Type
AJ71E71
IP address
192.168.0.19
Port No.
5001
Communication
UDP (fixed)
Содержание GOT2000 Series
Страница 2: ......
Страница 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 64: ......
Страница 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Страница 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Страница 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Страница 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Страница 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Страница 416: ......
Страница 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Страница 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Страница 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Страница 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Страница 542: ......
Страница 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Страница 568: ......
Страница 592: ...19 24 19 MULTI CHANNEL FUNCTION 19 3 GOT Side Settings Example Setting example for Ethernet connection 4 channels ...
Страница 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Страница 600: ......
Страница 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Страница 670: ...REVISIONS 2 ...
Страница 673: ......