9 Troubleshooting
9.2 LED status check
61
FX
3U
-64CCL User's Manual
1
Introduc
tion
2
Specifi
cation
and func
tion
3
Sy
stem
Configurati
on
4
Ins
tal
lation
5
W
iri
ng, S
tart-up
proced
ure
6
FX
3U
-64C
CL
settin
g (swi
tch
settin
g)
7
Buf
fer
M
emor
y
8
Program
Ex
ampl
e
9
Troubl
es
hooti
ng
A
Ve
rs
ion
Inform
ation
9.2
LED status check
The table below describes details for the LED statuses.
The POWER, RUN, L RUN, SD and RD LEDs are ON while the data link status is normal.
→
For details on troubleshooting by LED, refer to the master unit manual.
When the RUN LED does not light up and the hardware test is not set, the hardware may have an error.
For repair, contact your local Mitsubishi Electric distributor.
LED display
Color
Status
Status
POWER
Green
OFF
Power is not being supplied from the external power supply.
ON
Power is being supplied from the external power supply.
RUN
Green
OFF
64CCL has failed.
ON
Under 64CCL normal operation.
ERR.
Red
OFF
No errors.
ON
Error in the settings, error in the parameter details, error with the communication,
errors with the hardware.
L RUN
Green
OFF
Offline.
ON
Data link is being executed.
L ERR.
Red
OFF
No communication error.
Flicker
The switch setting was changed after start.
There is no terminating resistor.
Influence from noise.
ON
There is a data linking error.
There is a setting error.
SD
Green
OFF
Data is not being sent.
ON
Data is being sent.
RD
Green
OFF
Data is not being received.
ON
Data is being received.
Содержание FX3U-64CCL
Страница 1: ...FX3U 64CCL USER S MANUAL ...
Страница 2: ......
Страница 6: ... 4 MEMO ...
Страница 11: ...5 FX3U 64CCL User s Manual Table of Contents Warranty 69 Revised History 70 ...
Страница 77: ......